Chapter 7
.
Detailed Descriptions of EP-19xx Modules
GFK-2956A
November 2017
33
The maximum feed-in current in the output current path is 8 A. The module is sending a pulse (< 1
ms) every 100 ms.
Caution
Risk of material damage - In the case of a maximum power supply of 8 A and
a maximum temperature of +140 °F (+60 °C), all wired contacts on the fourth
connector must be connected with 1.5 mm² wiring.
5.5.1
LEDs
LED Indicators EP-1922
Module
Status
Green:
Communication over the system
bus
1.1
Yellow:
Safety circuit 0 OK
1.2
--
1.3
--
1.4
--
2.1
Yellow:
Safety circuit 1 OK
2.2
--
2.3
--
2.4
--
3.1
--
3.2
--
3.3
--
3.4
--
4.1
Yellow:
SS1 output active
4.2
Yellow:
24 V Safe output active
4.3
Green:
Feed-in voltage in valid range
4.4
--
For error Messages, refer to the Chapter,
LED Indicators and Troubleshooting.