Chapter 7
.
Detailed Descriptions of EP-19xx Modules
GFK-2956A
November 2017
21
Diagnosis
Module diagnosis
Yes
Individual channel diagnosis
Yes
Supply
Supply voltage
24 V dc +20%/-15% via system bus
External pre-fusing
mandatory: super fast, max. 8 A
Reverse battery protection
Yes
Current consumption (I
IN
in the power segment of
the Network Adapter), typ.
8 mA
Current consumption (I
IN
in the respective power
segment)
45 mA
General data
Weight
80 g (2.82 oz)
For additional general data, refer to the section,
Process Data
†
Byte
Bit
Description
Status
0
0
Safety input 0
0 - input inactive, 1 - input active
1
Reserved
2
Auto Start
0 - inactive, 1 - active
3
Man Start
0 - inactive, 1 - active
4
Safety input 0 / channel 1
0 - inactive, 1 - active
5
Safety input 0 / channel 2
0 - inactive, 1 - active
6
Reserved
7
Reserved
1
0
24 V Safet Output
0 - inactive, 1 - active
1
Reserved
2
24 V DC
0 - no feed in, 1 - power feed-in pending
3-7
Reserved
2
0-7
Reserved
3
0-7
Reserved
†
Standard data format