5
APPLICATION NOTES
5.1
RESET MECHANISMS FOR CB FAIL TIMERS
It is common practise to use low set undercurrent elements to indicate that circuit breaker poles have interrupted
the fault or load current. This covers the following situations:
●
Where circuit breaker auxiliary contacts are defective, or cannot be relied on to definitely indicate that the
breaker has tripped.
●
Where a circuit breaker has started to open but has become jammed. This may result in continued arcing at
the primary contacts, with an additional arcing resistance in the fault current path. Should this resistance
severely limit fault current, the initiating protection element may reset. Therefore, reset of the element may
not give a reliable indication that the circuit breaker has opened fully.
For any protection function requiring current to operate, the device uses operation of undercurrent elements to
detect that the necessary circuit breaker poles have tripped and reset the CB fail timers. However, the
undercurrent elements may not be reliable methods of resetting CBF in all applications. For example:
●
Where non-current operated protection, such as under/overvoltage or under/overfrequency, derives
measurements from a line connected voltage transformer. Here, I< only gives a reliable reset method if the
protected circuit would always have load current flowing. In this case, detecting drop-off of the initiating
protection element might be a more reliable method.
●
Where non-current operated protection, such as under/overvoltage or under/overfrequency, derives
measurements from a busbar connected voltage transformer. Again using I< would rely on the feeder
normally being loaded. Also, tripping the circuit breaker may not remove the initiating condition from the
busbar, and so drop-off of the protection element may not occur. In such cases, the position of the circuit
breaker auxiliary contacts may give the best reset method.
5.2
SETTING GUIDELINES (CB FAIL TIMER)
The following timing chart shows the CB Fail timing during normal and CB Fail operation. The maximum clearing
time should be less than the critical clearing time which is determined by a stability study. The CB Fail back-up trip
time delay considers the maximum CB clearing time, the CB Fail reset time plus a safety margin. Typical CB
clearing times are 1.5 or 3 cycles. The CB Fail reset time should be short enough to avoid CB Fail back-trip during
normal operation. Phase and ground undercurrent elements must be asserted for the CB Fail to reset. The
assertion of the undercurrent elements might be delayed due to the subsidence current that might be flowing
through the secondary AC circuit.
P64x
Chapter 10 - CB Fail Protection
P64x-TM-EN-1.3
233
Содержание P642
Страница 2: ......
Страница 18: ...Contents P64x xvi P64x TM EN 1 3 ...
Страница 24: ...Table of Figures P64x xxii P64x TM EN 1 3 ...
Страница 25: ...CHAPTER 1 INTRODUCTION ...
Страница 26: ...Chapter 1 Introduction P64x 2 P64x TM EN 1 3 ...
Страница 36: ...Chapter 1 Introduction P64x 12 P64x TM EN 1 3 ...
Страница 37: ...CHAPTER 2 SAFETY INFORMATION ...
Страница 38: ...Chapter 2 Safety Information P64x 14 P64x TM EN 1 3 ...
Страница 50: ...Chapter 2 Safety Information P64x 26 P64x TM EN 1 3 ...
Страница 51: ...CHAPTER 3 HARDWARE DESIGN ...
Страница 52: ...Chapter 3 Hardware Design P64x 28 P64x TM EN 1 3 ...
Страница 87: ...CHAPTER 4 SOFTWARE DESIGN ...
Страница 88: ...Chapter 4 Software Design P64x 64 P64x TM EN 1 3 ...
Страница 98: ...Chapter 4 Software Design P64x 74 P64x TM EN 1 3 ...
Страница 99: ...CHAPTER 5 CONFIGURATION ...
Страница 100: ...Chapter 5 Configuration P64x 76 P64x TM EN 1 3 ...
Страница 121: ...CHAPTER 6 TRANSFORMER DIFFERENTIAL PROTECTION ...
Страница 122: ...Chapter 6 Transformer Differential Protection P64x 98 P64x TM EN 1 3 ...
Страница 165: ...CHAPTER 7 TRANSFORMER CONDITION MONITORING ...
Страница 166: ...Chapter 7 Transformer Condition Monitoring P64x 142 P64x TM EN 1 3 ...
Страница 189: ...CHAPTER 8 RESTRICTED EARTH FAULT PROTECTION ...
Страница 190: ...Chapter 8 Restricted Earth Fault Protection P64x 166 P64x TM EN 1 3 ...
Страница 215: ...CHAPTER 9 CURRENT PROTECTION FUNCTIONS ...
Страница 216: ...Chapter 9 Current Protection Functions P64x 192 P64x TM EN 1 3 ...
Страница 249: ...CHAPTER 10 CB FAIL PROTECTION ...
Страница 250: ...Chapter 10 CB Fail Protection P64x 226 P64x TM EN 1 3 ...
Страница 259: ...CHAPTER 11 VOLTAGE PROTECTION FUNCTIONS ...
Страница 260: ...Chapter 11 Voltage Protection Functions P64x 236 P64x TM EN 1 3 ...
Страница 274: ...Chapter 11 Voltage Protection Functions P64x 250 P64x TM EN 1 3 ...
Страница 275: ...CHAPTER 12 FREQUENCY PROTECTION FUNCTIONS ...
Страница 276: ...Chapter 12 Frequency Protection Functions P64x 252 P64x TM EN 1 3 ...
Страница 286: ...Chapter 12 Frequency Protection Functions P64x 262 P64x TM EN 1 3 ...
Страница 287: ...CHAPTER 13 MONITORING AND CONTROL ...
Страница 288: ...Chapter 13 Monitoring and Control P64x 264 P64x TM EN 1 3 ...
Страница 306: ...Chapter 13 Monitoring and Control P64x 282 P64x TM EN 1 3 ...
Страница 307: ...CHAPTER 14 SUPERVISION ...
Страница 308: ...Chapter 14 Supervision P64x 284 P64x TM EN 1 3 ...
Страница 322: ...Chapter 14 Supervision P64x 298 P64x TM EN 1 3 ...
Страница 323: ...CHAPTER 15 DIGITAL I O AND PSL CONFIGURATION ...
Страница 324: ...Chapter 15 Digital I O and PSL Configuration P64x 300 P64x TM EN 1 3 ...
Страница 336: ...Chapter 15 Digital I O and PSL Configuration P64x 312 P64x TM EN 1 3 ...
Страница 337: ...CHAPTER 16 COMMUNICATIONS ...
Страница 338: ...Chapter 16 Communications P64x 314 P64x TM EN 1 3 ...
Страница 397: ...CHAPTER 17 CYBER SECURITY ...
Страница 398: ...Chapter 17 Cyber Security P64x 374 P64x TM EN 1 3 ...
Страница 415: ...CHAPTER 18 INSTALLATION ...
Страница 416: ...Chapter 18 Installation P64x 392 P64x TM EN 1 3 ...
Страница 429: ...5 2 CASE DIMENSIONS 60TE E01409 Figure 167 60TE case dimensions P64x Chapter 18 Installation P64x TM EN 1 3 405 ...
Страница 431: ...CHAPTER 19 COMMISSIONING INSTRUCTIONS ...
Страница 432: ...Chapter 19 Commissioning Instructions P64x 408 P64x TM EN 1 3 ...
Страница 454: ...V01505 Figure 173 Harmonic Restraint Test Plane Chapter 19 Commissioning Instructions P64x 430 P64x TM EN 1 3 ...
Страница 460: ...Chapter 19 Commissioning Instructions P64x 436 P64x TM EN 1 3 ...
Страница 461: ...CHAPTER 20 MAINTENANCE AND TROUBLESHOOTING ...
Страница 462: ...Chapter 20 Maintenance and Troubleshooting P64x 438 P64x TM EN 1 3 ...
Страница 477: ...CHAPTER 21 TECHNICAL SPECIFICATIONS ...
Страница 478: ...Chapter 21 Technical Specifications P64x 454 P64x TM EN 1 3 ...
Страница 507: ...APPENDIX A ORDERING OPTIONS ...
Страница 508: ...Appendix A Ordering Options P64x P64x TM EN 1 3 ...
Страница 512: ...Appendix A Ordering Options P64x A4 P64x TM EN 1 3 ...
Страница 513: ...APPENDIX B SETTINGS AND SIGNALS ...
Страница 515: ...APPENDIX C WIRING DIAGRAMS ...
Страница 516: ...Appendix C Wiring Diagrams P64x P64x TM EN 1 3 ...
Страница 590: ......
Страница 591: ......