THERMAL OVERLOAD PROTECTION
Transformer overheating can be caused due to failures of the cooling system, external faults that are not cleared
promptly, or overload and abnormal system conditions. These abnormal conditions include low frequency, high
voltage, non-sinusoidal load current, or phase-voltage imbalance.
Overheating shortens the life of the transformer insulation in proportion to the duration and magnitude of the high
temperature. If excessive, this may even result in an immediate insulation failure. Overheating can also generate
gases that could result in electrical failure, or cause the transformer coolant to be heated above its flashpoint
temperature, introducing the risk of fire.
Studies suggest that the life of insulation is approximately halved for each 10°C rise in temperature above the
rated value. However, the life of insulation is not wholly dependent on the rise in temperature but on the time the
insulation is subjected to this elevated temperature. Due to the relatively large heat storage capacity of a
transformer, infrequent overloads of short duration may not damage it. However, sustained overloads of a few
percent may result in premature aging and consequent insulation failure.
Transformer thermal overload protection is designed to protect equipment from sustained overload. Thermal
overload protection allows modest but transient overload conditions to occur, while tripping for sustained
overloads, which would not be detected by standard overcurrent protection.
Transformer Losses
The losses in a transformer are shown in the following diagram:
V03200
Transformer Losses
Load Losses
No Load Losses
Copper Losses
Eddy-current Losses
Hysteresis Losses
Stray Losses
Apparent Losses
Core Losses
(Iron Losses)
Figure 62: Transformer losses
The flow of the magnetising current through the resistance of the winding creates a real but generally relatively
small I
2
R loss and voltage drop. The loss that is due to this magnetizing current in the primary winding is called the
apparent loss.
Time-varying fluxes in iron-based materials, cause losses called core losses, or iron losses. These iron losses are
divided into two categories; hysteresis losses and eddy-current losses.
The sum of copper losses and the stray losses is called the load loss. Copper losses are due to the flow of load
currents through the primary and secondary windings. They are equal to I
2
R, and they heat up the wires and
cause voltage drops. Stray losses are due to the stray capacitance and leakage inductance. Stray capacitance
exists between turns, between one winding and another, and between windings and the core.
2.1
THERMAL OVERLOAD IMPLEMENTATION
The thermal overload protection in this device is based on the IEEE Standard C57.91-1995. It provides thermal
overload protection for either an individual winding or the transformer as a whole. The thermal overload
protection settings are in the THERMAL OVERLOAD column.
Chapter 7 - Transformer Condition Monitoring
P64x
144
P64x-TM-EN-1.3
Содержание P642
Страница 2: ......
Страница 18: ...Contents P64x xvi P64x TM EN 1 3 ...
Страница 24: ...Table of Figures P64x xxii P64x TM EN 1 3 ...
Страница 25: ...CHAPTER 1 INTRODUCTION ...
Страница 26: ...Chapter 1 Introduction P64x 2 P64x TM EN 1 3 ...
Страница 36: ...Chapter 1 Introduction P64x 12 P64x TM EN 1 3 ...
Страница 37: ...CHAPTER 2 SAFETY INFORMATION ...
Страница 38: ...Chapter 2 Safety Information P64x 14 P64x TM EN 1 3 ...
Страница 50: ...Chapter 2 Safety Information P64x 26 P64x TM EN 1 3 ...
Страница 51: ...CHAPTER 3 HARDWARE DESIGN ...
Страница 52: ...Chapter 3 Hardware Design P64x 28 P64x TM EN 1 3 ...
Страница 87: ...CHAPTER 4 SOFTWARE DESIGN ...
Страница 88: ...Chapter 4 Software Design P64x 64 P64x TM EN 1 3 ...
Страница 98: ...Chapter 4 Software Design P64x 74 P64x TM EN 1 3 ...
Страница 99: ...CHAPTER 5 CONFIGURATION ...
Страница 100: ...Chapter 5 Configuration P64x 76 P64x TM EN 1 3 ...
Страница 121: ...CHAPTER 6 TRANSFORMER DIFFERENTIAL PROTECTION ...
Страница 122: ...Chapter 6 Transformer Differential Protection P64x 98 P64x TM EN 1 3 ...
Страница 165: ...CHAPTER 7 TRANSFORMER CONDITION MONITORING ...
Страница 166: ...Chapter 7 Transformer Condition Monitoring P64x 142 P64x TM EN 1 3 ...
Страница 189: ...CHAPTER 8 RESTRICTED EARTH FAULT PROTECTION ...
Страница 190: ...Chapter 8 Restricted Earth Fault Protection P64x 166 P64x TM EN 1 3 ...
Страница 215: ...CHAPTER 9 CURRENT PROTECTION FUNCTIONS ...
Страница 216: ...Chapter 9 Current Protection Functions P64x 192 P64x TM EN 1 3 ...
Страница 249: ...CHAPTER 10 CB FAIL PROTECTION ...
Страница 250: ...Chapter 10 CB Fail Protection P64x 226 P64x TM EN 1 3 ...
Страница 259: ...CHAPTER 11 VOLTAGE PROTECTION FUNCTIONS ...
Страница 260: ...Chapter 11 Voltage Protection Functions P64x 236 P64x TM EN 1 3 ...
Страница 274: ...Chapter 11 Voltage Protection Functions P64x 250 P64x TM EN 1 3 ...
Страница 275: ...CHAPTER 12 FREQUENCY PROTECTION FUNCTIONS ...
Страница 276: ...Chapter 12 Frequency Protection Functions P64x 252 P64x TM EN 1 3 ...
Страница 286: ...Chapter 12 Frequency Protection Functions P64x 262 P64x TM EN 1 3 ...
Страница 287: ...CHAPTER 13 MONITORING AND CONTROL ...
Страница 288: ...Chapter 13 Monitoring and Control P64x 264 P64x TM EN 1 3 ...
Страница 306: ...Chapter 13 Monitoring and Control P64x 282 P64x TM EN 1 3 ...
Страница 307: ...CHAPTER 14 SUPERVISION ...
Страница 308: ...Chapter 14 Supervision P64x 284 P64x TM EN 1 3 ...
Страница 322: ...Chapter 14 Supervision P64x 298 P64x TM EN 1 3 ...
Страница 323: ...CHAPTER 15 DIGITAL I O AND PSL CONFIGURATION ...
Страница 324: ...Chapter 15 Digital I O and PSL Configuration P64x 300 P64x TM EN 1 3 ...
Страница 336: ...Chapter 15 Digital I O and PSL Configuration P64x 312 P64x TM EN 1 3 ...
Страница 337: ...CHAPTER 16 COMMUNICATIONS ...
Страница 338: ...Chapter 16 Communications P64x 314 P64x TM EN 1 3 ...
Страница 397: ...CHAPTER 17 CYBER SECURITY ...
Страница 398: ...Chapter 17 Cyber Security P64x 374 P64x TM EN 1 3 ...
Страница 415: ...CHAPTER 18 INSTALLATION ...
Страница 416: ...Chapter 18 Installation P64x 392 P64x TM EN 1 3 ...
Страница 429: ...5 2 CASE DIMENSIONS 60TE E01409 Figure 167 60TE case dimensions P64x Chapter 18 Installation P64x TM EN 1 3 405 ...
Страница 431: ...CHAPTER 19 COMMISSIONING INSTRUCTIONS ...
Страница 432: ...Chapter 19 Commissioning Instructions P64x 408 P64x TM EN 1 3 ...
Страница 454: ...V01505 Figure 173 Harmonic Restraint Test Plane Chapter 19 Commissioning Instructions P64x 430 P64x TM EN 1 3 ...
Страница 460: ...Chapter 19 Commissioning Instructions P64x 436 P64x TM EN 1 3 ...
Страница 461: ...CHAPTER 20 MAINTENANCE AND TROUBLESHOOTING ...
Страница 462: ...Chapter 20 Maintenance and Troubleshooting P64x 438 P64x TM EN 1 3 ...
Страница 477: ...CHAPTER 21 TECHNICAL SPECIFICATIONS ...
Страница 478: ...Chapter 21 Technical Specifications P64x 454 P64x TM EN 1 3 ...
Страница 507: ...APPENDIX A ORDERING OPTIONS ...
Страница 508: ...Appendix A Ordering Options P64x P64x TM EN 1 3 ...
Страница 512: ...Appendix A Ordering Options P64x A4 P64x TM EN 1 3 ...
Страница 513: ...APPENDIX B SETTINGS AND SIGNALS ...
Страница 515: ...APPENDIX C WIRING DIAGRAMS ...
Страница 516: ...Appendix C Wiring Diagrams P64x P64x TM EN 1 3 ...
Страница 590: ......
Страница 591: ......