manualshive.com logo in svg
background image

Page 18 of 25

508133G01 / 31-5000715

Issue 2140

4.  The unit will display the unit type for 10 seconds. Press 

the push button and hold it for 3 seconds for the unit 

to store the unit type. Once, the unit code is stored 

the system acknowledges by displaying a string of 

characters ending with the updated system unit code.

After programming of unit type is complete, the unit can be 

set up for charge mode operation.

Charge Mode Jumper

To initiate the NS18HMA  Charge Mode function, install 

the jumper across the two Charge Mode Pins (CHRG 

MODE) on the outdoor control. The Charge Mode can be 

used when charging the system with refrigerant, checking 

the refrigerant charge, pumping down the system and 

performing other service procedures that requires outdoor 

unit operation at 100% capacity.

NS18HMA 

Charge Mode Operation with a Conventional 

24VAC Heat Pump Thermostat

Charge Mode Display String

When unit is in the charge mode, Suction Pressure 

(SPxxx), Suction Temp (Stxx.x), Superheat (SHxx.x), Liquid 

Pressure (LPxxx), Liquid Temp (Ltxx.x) and Subcooling 

(SCxx.x) will be scrolled on the 7-segment display.

Example:

S P 1 3 5

 pause 

S t 6 2

 pause 

S H 1 5

 pause 

L P 3 4 5 

pause 

L t 9 6

 pause 

S C 1 0

 repeat

Charge Mode Jumper Operation in the Cooling Mode

On applications with a conventional 24VAC heat pump 

thermostat, the charge mode jumper must be installed on 

the Charge Mode Pins after providing a cooling compressor 

demand to the NS18HMA  and an “O” cooling reversing 

valve demand to initiate the Charge Mode. A cooling 

blower demand must also be provided to initiate blower in 

high stage operation on the indoor unit.

The compressor and outdoor fan motor will begin to ramp 

up and reach 100% design capacity within 3 minutes. They 

will continue to operate at 100% design capacity for the 

duration of charge mode. 

Charge Mode Jumper Operation in the Heat Pump 

Heating Mode

On applications with a conventional 24VAC heat pump 

thermostat, the charge mode jumper must be installed 

on the Charge Mode Pins after providing a heating 

compressor demand to the NS18HMA  without an “O” 

reversing valve signal to initiate the Charge Mode. A 

heating blower demand must also be provided to initiate 

high speed blower operation on the indoor unit. 

The compressor and outdoor fan motor will begin to ramp 

up and reach 100% design capacity within 3 minutes. They 

will continue to operate at 100% design capacity for the 

duration of charge mode. 

Exiting Charge Mode

To exit the charging mode, remove the Charge Mode 

Jumper from the Charge Mode Pins. The system will 

be in Charge Mode for a maximum time of 60 minutes 

and will automatically exit the charge mode and resume 

normal operation after 60 minutes even if the charge mode 

jumper is left in place. To extend the charge mode beyond 

60  minutes,  ensure  the  cooling/heating  demand,  blower 

demand and appropriate reversing valve demand are 

available and reapply the charge mode jumper. 

NOTE: 

If compressor demand is lost during charge mode 

period, then the compressor and fan will cease to operate, 

and  the  unit  will  enter  into  a  delay  timer  for  3  minutes. 

Repeat  the  charging  mode  procedure  to  get  back  into 

charge mode.

Cooling Operation Mode Jumper

The Cooling Operation Mode Jumper is only used on 

applications installed with a conventional 24VAC heat 

pump thermostat. In applications with a conventional 

24VAC heat pump thermostat, the compressor capacity is 

controlled to maintain the target suction pressure setpoint. 

The Cooling Operation Mode Jumper has three selectable 

cooling modes. The three modes are Efficiency (Jumper 

installed on Pins 1 & 2), Normal Mode (Jumper installed 

on Pins 2 & 3) and Comfort Mode (Jumper Removed). 

The  factory  default  position  is  the  Efficiency  Mode.  The 

Efficiency mode has a variable suction pressure setpoint 

that will vary with the outdoor temperature; as the outdoor 

temperature increases the suction pressure setpoint will 

decrease. When the Cooling Operation Mode jumper 

is installed in the “Normal Mode” the suction pressure 

setpoint is 135 psig.

When the Cooling Operation Mode jumper is installed in 

the “Comfort Mode” the suction pressure setpoint is 125 

psig.

Operation Mode 

Jumper

Jumper 

Position

Target Suction 

Pressure Setting

Efficiency (default)

Pin 1 to Pin 2

Variable based on OAT

Normal

Pin 2 to Pin 3

135 PSIG

Comfort

Jumper Off

125 PSIG

Table 9. Cooling Operation Mode Jumper 

(Conventional 24VAC Thermostats Only)

Содержание NS18HMA

Страница 1: ...ion and service performed by unqualified persons can result in property damage personal injury or death WARNING Sharp metal edges can cause injury When installing the unit use care to avoid sharp edge...

Страница 2: ...ll safety codes Wear safety glasses and work gloves Use quenching cloth for brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warning or cautions at...

Страница 3: ...m building not to exceed 1 4 per foot Figure 1 Slab Mounting Install on a Solid Level Mounting Pad The outdoor section is to be installed on a solid foundation This foundation should extend a minimum...

Страница 4: ...warranty will be void if the drier is not installed Installation of Line Sets DO NOT fasten liquid or suction lines in direct contact with the floor or ceiling joist Use an insulated or suspension typ...

Страница 5: ...listed in Table 3 Between 51 and 150 Linear Feet Crankcase heater and nonbleed port TXV factory installed No additional components required Vertical vapor riser must be sized to the vapor riser liste...

Страница 6: ...iquid line size shaded row on the outdoor tonnage C Select the actual Total Linear Length of your system shown at the top of the table D The elevation listed in the table is the maximum allowed for th...

Страница 7: ...ponents including line set and indoor coil must be an AHRI match with the unit in order to fulfill unit warranty requirements Fire Explosion and Personal Safety hazard Failure to follow this warning c...

Страница 8: ...around the stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil 4 Attach the stubbed end of the check expans...

Страница 9: ...ain round Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE...

Страница 10: ...all water saturated cloths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazin...

Страница 11: ...sig 1034 kPa Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that...

Страница 12: ...r liquid refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cyli...

Страница 13: ...1 is jumpered to Y2 in the outdoor unit Note that the published performance data is based upon the use of a two stage thermostat Refer to the NS18HMA field wiring diagram for a conventional 24VAC sing...

Страница 14: ...hermostat Control Options Size Circuit and Install Service Disconnect Switch Refer to the unit nameplate for minimum circuit ampacity and maximum fuse or circuit breaker HACR per NEC Install power wir...

Страница 15: ...100 30m 18 Temperature Rating 35 C Minimum More than 100 30m 16 Table 7 Conventional 24VAC Thermostat Wiring Route High Voltage and Ground Wires Any excess high voltage field wiring should be trimmed...

Страница 16: ...RMOSTAT W L Y2 Y1 O DS C I I R DF TST Y1 O C W1 R G TC TO ACC2 ACC1 Y1 O DH C W2 W1 R G DS W2 FOR SINGLE STAGE OPERATION INSTALL A JUMPER BETWEEN Y1 TO Y2 ON THE OUTDOOR UNIT TERMINAL STRIP Figure 9 C...

Страница 17: ...If the intended capacity for the application is 3 or 5 Ton skip this section The units are field convertible to 2 Ton or 4 Ton to efficiently perform for the required application If the intended capa...

Страница 18: ...itiate the Charge Mode A heating blower demand must also be provided to initiate high speed blower operation on the indoor unit The compressor and outdoor fan motor will begin to ramp up and reach 100...

Страница 19: ...ooling indoor blower operation In single stage thermostat applications a jumper must be installed between Y1 and Y2 on the NS18HMA outdoor control The compressor will be controlled in the variable cap...

Страница 20: ...late to list the actual field charge Table 11 Refrigerant Charge Adjustment Liquid Line Set Diameter Oz Per 5 ft adjust from 15 ft line set 3 8 in 3 oz per 5 ft or 0 6 oz per 1 ft If line length is gr...

Страница 21: ...testing is completed replace service port cap Tighten finger tight then an additional 1 6 turn To Open Liquid or Suction Line Service Valve 1 Remove stem cap with an adjustable wrench 2 Use service wr...

Страница 22: ...in mild detergent and rinsing with cold water Allow filter to dry before reinstalling Replace filters with the arrows pointing in the direction of airflow Dirty filters are the most common cause of p...

Страница 23: ...heat pump to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings Many heat pump thermostats are also equipped with an emergency heat mode which locks out...

Страница 24: ...Page 24 of 25 508133G01 31 5000715 Issue 2140 Figure 15 Wiring Diagram...

Страница 25: ...____________ Actual Amps ______ Rated Volts _______ Actual Volts ________ Condenser Fan Full Load Amps _________ Actual Amps ______ Cooling Mode Suction Pressure ____________________ Liquid Pressure _...

Отзывы: