Electrical - Circuit Sizing and Wire Routing

In the U.S.A., wiring must conform with current local codes 

and the current National Electric Code (NEC). In Canada, 

wiring must conform with current local codes and the 

current Canadian Electrical Code (CEC).

Refer to the furnace or air handler installation instructions 

for additional wiring application diagrams and refer to unit 

nameplate for minimum circuit ampacity and maximum 

overcurrent protection size.

24VAC Transformer

Use the transformer provided with the furnace or air handler 

for low-voltage control power (24VAC - 40 VA minimum).

Thermostat Control and Low Voltage 

Control Wiring

Conventional 24VAC Thermostat Control

The  NS18HMA  variable capacity unit may be installed 

using a conventional 24VAC two-stage cooling or single-

stage cooling thermostat.

The  NS18HMA  unit will provide full variable capacity 

operation when installed with a conventional 24VAC two 

stage heat pump or single-stage heat pump thermostat. 

The  NS18HMA  outdoor control has advanced control 

algorithms, which provide true variable speed capacity 

operation by modulating the compressor speed to achieve 

the target suction pressure set point in cooling mode, and 

liquid pressure set point in heating mode.

When utilizing a two-stage conventional 24VAC thermostat, 

six wires are required to control the outdoor unit (R, C, W1, 

O, Y1 and Y2). Refer to the NS18HMA 

field wiring diagram 

for a conventional 24VAC two-stage thermostat.

When utilizing a single conventional 24VAC thermostat, 

five wires are required to control the outdoor unit (R, C, W1, 

O, and Y1) and Y1 is jumpered to Y2 in the outdoor unit. 

Note that the published performance data is based upon 

the use of a two-stage thermostat. Refer to the NS18HMA 

field wiring diagram for a conventional 24VAC single-stage 

thermostat.

NS18HMA Low Voltage Control Wiring 

Connections

The  NS18HMA  variable capacity units are provided with 

(2)  RAST  6-Pin  connections  for  connecting  the  field  low 

voltage control wiring to the NS18HMA harnesses in the low 

voltage control make-up box. One RAST 6-pin connector is 

labeled with terminals TST, DF, R, I+, I- and C. The second 

RAST 6-pin connector is labeled with terminals DS, O, Y1, 

Y2, L and W.

Electrical Shock Hazard! 

Can cause injury or death. Unit must be 

properly grounded in accordance with 

national and local codes.
Line voltage is present at all components 

when unit is not in operation on units 

with single-pole contactors. Disconnect 

all remote electric power supplies before 

opening access panel. Unit may have 

multiple power supplies.

 WARNING

Fire Hazard. Use of aluminum wire with this product 

may result in a fire, causing property damage, severe 

injury or death. Use copper wire only with this product.

 WARNING

Failure to use properly sized wiring and circuit breaker 

may result in property damage. Size wiring and circuit 

breaker(s) per Technical Specifications and unit rating 

plate.

 WARNING

ELECTROSTATIC DISCHARGE (ESD)

Precautions and Procedures

Electrostatic discharge can affect electronic components. 

Take care during unit installation and service to protect 

the unit’s electronic controls. Precautions will help to 

avoid control exposure to electrostatic discharge by 

putting the unit, the control and the technician at the 

same electrostatic potential. Touch hand and all tools 

on an unpainted unit surface before performing any 

service procedure to neutralize electrostatic charge.

 WARNING

Содержание NS18HMA

Страница 1: ...ion and service performed by unqualified persons can result in property damage personal injury or death WARNING Sharp metal edges can cause injury When installing the unit use care to avoid sharp edge...

Страница 2: ...ll safety codes Wear safety glasses and work gloves Use quenching cloth for brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warning or cautions at...

Страница 3: ...m building not to exceed 1 4 per foot Figure 1 Slab Mounting Install on a Solid Level Mounting Pad The outdoor section is to be installed on a solid foundation This foundation should extend a minimum...

Страница 4: ...warranty will be void if the drier is not installed Installation of Line Sets DO NOT fasten liquid or suction lines in direct contact with the floor or ceiling joist Use an insulated or suspension typ...

Страница 5: ...listed in Table 3 Between 51 and 150 Linear Feet Crankcase heater and nonbleed port TXV factory installed No additional components required Vertical vapor riser must be sized to the vapor riser liste...

Страница 6: ...iquid line size shaded row on the outdoor tonnage C Select the actual Total Linear Length of your system shown at the top of the table D The elevation listed in the table is the maximum allowed for th...

Страница 7: ...ponents including line set and indoor coil must be an AHRI match with the unit in order to fulfill unit warranty requirements Fire Explosion and Personal Safety hazard Failure to follow this warning c...

Страница 8: ...around the stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil 4 Attach the stubbed end of the check expans...

Страница 9: ...ain round Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE...

Страница 10: ...all water saturated cloths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazin...

Страница 11: ...sig 1034 kPa Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that...

Страница 12: ...r liquid refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cyli...

Страница 13: ...1 is jumpered to Y2 in the outdoor unit Note that the published performance data is based upon the use of a two stage thermostat Refer to the NS18HMA field wiring diagram for a conventional 24VAC sing...

Страница 14: ...hermostat Control Options Size Circuit and Install Service Disconnect Switch Refer to the unit nameplate for minimum circuit ampacity and maximum fuse or circuit breaker HACR per NEC Install power wir...

Страница 15: ...100 30m 18 Temperature Rating 35 C Minimum More than 100 30m 16 Table 7 Conventional 24VAC Thermostat Wiring Route High Voltage and Ground Wires Any excess high voltage field wiring should be trimmed...

Страница 16: ...RMOSTAT W L Y2 Y1 O DS C I I R DF TST Y1 O C W1 R G TC TO ACC2 ACC1 Y1 O DH C W2 W1 R G DS W2 FOR SINGLE STAGE OPERATION INSTALL A JUMPER BETWEEN Y1 TO Y2 ON THE OUTDOOR UNIT TERMINAL STRIP Figure 9 C...

Страница 17: ...If the intended capacity for the application is 3 or 5 Ton skip this section The units are field convertible to 2 Ton or 4 Ton to efficiently perform for the required application If the intended capa...

Страница 18: ...itiate the Charge Mode A heating blower demand must also be provided to initiate high speed blower operation on the indoor unit The compressor and outdoor fan motor will begin to ramp up and reach 100...

Страница 19: ...ooling indoor blower operation In single stage thermostat applications a jumper must be installed between Y1 and Y2 on the NS18HMA outdoor control The compressor will be controlled in the variable cap...

Страница 20: ...late to list the actual field charge Table 11 Refrigerant Charge Adjustment Liquid Line Set Diameter Oz Per 5 ft adjust from 15 ft line set 3 8 in 3 oz per 5 ft or 0 6 oz per 1 ft If line length is gr...

Страница 21: ...testing is completed replace service port cap Tighten finger tight then an additional 1 6 turn To Open Liquid or Suction Line Service Valve 1 Remove stem cap with an adjustable wrench 2 Use service wr...

Страница 22: ...in mild detergent and rinsing with cold water Allow filter to dry before reinstalling Replace filters with the arrows pointing in the direction of airflow Dirty filters are the most common cause of p...

Страница 23: ...heat pump to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings Many heat pump thermostats are also equipped with an emergency heat mode which locks out...

Страница 24: ...Page 24 of 25 508133G01 31 5000715 Issue 2140 Figure 15 Wiring Diagram...

Страница 25: ...____________ Actual Amps ______ Rated Volts _______ Actual Volts ________ Condenser Fan Full Load Amps _________ Actual Amps ______ Cooling Mode Suction Pressure ____________________ Liquid Pressure _...

Отзывы: