manualshive.com logo in svg
background image

Page 20 of 25

508133G01 / 31-5000715

Issue 2140

Start-Up

If unit is equipped with a crankcase heater, it should 

be energized 24 hours before unit start-up to prevent 

compressor damage as a result of slugging.

 CAUTION

1.  Rotate fan to check for frozen bearings or binding.
2. 

Inspect all factory and field-installed wiring for loose 

connections.

3.  After evacuation is complete, open liquid line and 

suction line service valves to release refrigerant 

charge (contained in outdoor unit) into system.

4. 

Replace the stem caps and secure finger tight, then 

tighten an additional 1/6 of a turn.

5.  Check voltage supply at the disconnect switch. The 

voltage must be within the range listed on the unit 

nameplate. If not, do not start equipment until the 

power company has been consulted and the voltage 

condition corrected.

6.  Set thermostat for cooling demand, turn on power to 

indoor blower, and close the outdoor unit disconnect 

switch to start the unit.

7.  Recheck unit voltage with unit running. Power must be 

within range shown on unit nameplate.

Refrigerant Charging

Excessive amounts of liquid refrigerant entering the 

suction line can damage the compressor. When adding 

refrigerant, precautions must be taken to control the 

flow of liquid into the system. This can be done by using 

a liquid vaporizing adapter or manual control using a 

sight glass as indicator. 

 CAUTION

Units are factory charged with the amount of R-410A 

refrigerant indicated on the unit rating plate. This charge is 

based on a matching indoor coil and outdoor coil with 15’ 

line set. For varying lengths of line set, refer to Table 11 for 

refrigerant charge adjustment. A blank space is provided 

on the unit rating plate to list the actual field charge.

Table 11. Refrigerant Charge Adjustment

Liquid Line Set Diameter

Oz. Per 5 ft. adjust from 15 

ft. line set*

3/8 in.

3 oz. per 5 ft. 

 or 0.6 oz. per 1 ft.

* If line length is greater than 15 ft., add this amount. If line 

length is less than 15 ft., remove this amount.

Mineral oils are not compatible with R-410A. If oil must 

be added, it must be a polyolester oil.

 IMPORTANT

NOTE: 

Both  airflow  and  refrigerant  charge  must  be 

monitored for proper system set-up. It may be necessary to 

alternately check and adjust the airflow and the refrigerant 

charge.

If the system is void of refrigerant, or if the outdoor ambient 

temperature is cool, use the weigh-in method to charge the 

unit. Do this after any leaks have been repaired.
1.  Recover the refrigerant from the unit.
2.  Conduct a leak check, then evacuate as previously 

outlined.

3.  Weigh in the charge according to the total amount 

shown on the unit nameplate.

If weighing facilities are not available or if unit is being 

charged during warm weather, use one of the following 

procedures.

•  For systems using a TXV on the indoor evaporator 

and outdoor temperature above 60°F

 – charge in 

cooling mode using the subcooling method and table 

provided on the unit access panel.

•  For systems below 60°F

 – charge in heating mode 

using the subcooling method and table provided on 

the unit access panel. Attach low pressure gauge 

hose to auxiliary service port to access suction side in 

heating mode.

NOTE: 

All unit table values are based on 70 to 80°F 

indoor  return  air  temperature  for  cooling  mode,  and 

65

°

F to 75°F return air temperature for heat mode.

High Pressure Switch

This unit is equipped with a high pressure switch which 

is located on the liquid line. The SPST, normally closed 

pressure switch opens when liquid line pressure rises above 

the  factory  setting  of  590  +/-  15  psig  and  automatically 

resets at 418 +/- 15 psig.

Содержание NS18HMA

Страница 1: ...ion and service performed by unqualified persons can result in property damage personal injury or death WARNING Sharp metal edges can cause injury When installing the unit use care to avoid sharp edge...

Страница 2: ...ll safety codes Wear safety glasses and work gloves Use quenching cloth for brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warning or cautions at...

Страница 3: ...m building not to exceed 1 4 per foot Figure 1 Slab Mounting Install on a Solid Level Mounting Pad The outdoor section is to be installed on a solid foundation This foundation should extend a minimum...

Страница 4: ...warranty will be void if the drier is not installed Installation of Line Sets DO NOT fasten liquid or suction lines in direct contact with the floor or ceiling joist Use an insulated or suspension typ...

Страница 5: ...listed in Table 3 Between 51 and 150 Linear Feet Crankcase heater and nonbleed port TXV factory installed No additional components required Vertical vapor riser must be sized to the vapor riser liste...

Страница 6: ...iquid line size shaded row on the outdoor tonnage C Select the actual Total Linear Length of your system shown at the top of the table D The elevation listed in the table is the maximum allowed for th...

Страница 7: ...ponents including line set and indoor coil must be an AHRI match with the unit in order to fulfill unit warranty requirements Fire Explosion and Personal Safety hazard Failure to follow this warning c...

Страница 8: ...around the stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil 4 Attach the stubbed end of the check expans...

Страница 9: ...ain round Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE...

Страница 10: ...all water saturated cloths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazin...

Страница 11: ...sig 1034 kPa Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that...

Страница 12: ...r liquid refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cyli...

Страница 13: ...1 is jumpered to Y2 in the outdoor unit Note that the published performance data is based upon the use of a two stage thermostat Refer to the NS18HMA field wiring diagram for a conventional 24VAC sing...

Страница 14: ...hermostat Control Options Size Circuit and Install Service Disconnect Switch Refer to the unit nameplate for minimum circuit ampacity and maximum fuse or circuit breaker HACR per NEC Install power wir...

Страница 15: ...100 30m 18 Temperature Rating 35 C Minimum More than 100 30m 16 Table 7 Conventional 24VAC Thermostat Wiring Route High Voltage and Ground Wires Any excess high voltage field wiring should be trimmed...

Страница 16: ...RMOSTAT W L Y2 Y1 O DS C I I R DF TST Y1 O C W1 R G TC TO ACC2 ACC1 Y1 O DH C W2 W1 R G DS W2 FOR SINGLE STAGE OPERATION INSTALL A JUMPER BETWEEN Y1 TO Y2 ON THE OUTDOOR UNIT TERMINAL STRIP Figure 9 C...

Страница 17: ...If the intended capacity for the application is 3 or 5 Ton skip this section The units are field convertible to 2 Ton or 4 Ton to efficiently perform for the required application If the intended capa...

Страница 18: ...itiate the Charge Mode A heating blower demand must also be provided to initiate high speed blower operation on the indoor unit The compressor and outdoor fan motor will begin to ramp up and reach 100...

Страница 19: ...ooling indoor blower operation In single stage thermostat applications a jumper must be installed between Y1 and Y2 on the NS18HMA outdoor control The compressor will be controlled in the variable cap...

Страница 20: ...late to list the actual field charge Table 11 Refrigerant Charge Adjustment Liquid Line Set Diameter Oz Per 5 ft adjust from 15 ft line set 3 8 in 3 oz per 5 ft or 0 6 oz per 1 ft If line length is gr...

Страница 21: ...testing is completed replace service port cap Tighten finger tight then an additional 1 6 turn To Open Liquid or Suction Line Service Valve 1 Remove stem cap with an adjustable wrench 2 Use service wr...

Страница 22: ...in mild detergent and rinsing with cold water Allow filter to dry before reinstalling Replace filters with the arrows pointing in the direction of airflow Dirty filters are the most common cause of p...

Страница 23: ...heat pump to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings Many heat pump thermostats are also equipped with an emergency heat mode which locks out...

Страница 24: ...Page 24 of 25 508133G01 31 5000715 Issue 2140 Figure 15 Wiring Diagram...

Страница 25: ...____________ Actual Amps ______ Rated Volts _______ Actual Volts ________ Condenser Fan Full Load Amps _________ Actual Amps ______ Cooling Mode Suction Pressure ____________________ Liquid Pressure _...

Отзывы: