GEK-113308
MIWII Directional Power Protection System
5-3
5 SETTINGS
5.2 MAIN SETTINGS
5
5.2.3 FUNCTION 32 1 (MIWII1000/MIWII2000)
5.2.4 FUNCTION 32 2 (MIWII1000/MIWII2000)
5.2.5 FUNCTION 32 3 (MIWII1000/MIWII2000)
ENERVISTA MII SETUP
HMI
DEFAULT
RANGE
STEP
FUNCTION 32 1
32_1 FUNCTION
FUNCTION 32 1
Enable 32 1
32_1 Enable
Enable 32 1
NO
YES/NO
NA
Trip Enable 32 1
32_1 Trip
Trip Enable 32 1
DISABLE
READY / DISABLE
NA
Power 32 1
32_1 Power Type
Power 32 1
ACTIVE
ACTIVE / REACTIVE APPARENT NA
Type 32 1
32_1 Minimum/Maximum
Type 32 1
MINIMUM
MINIMUM / MAXIMUM
NA
Direction 32 1
32_1 Forward/Reverse
Direction 32 1
FORWARD
FORWARD / REVERSE
NA
Alarm Level 32 1
32_1 Alarm Level
Alarm Level 32 1
0.05
0.01 - 1.50
0.01
Alarm Delay 32 1
32_1 Alarm Delay
Alarm Delay 32 1
10 s
0.2 – 120 s
0.1
Trip Level 32 1
32_1 Trip Level
Trip Level 32 1
0.05 pu
0.01 - 1.50
0.01
Trip Delay 32 1
32_1 Trip Delay
Trip Delay 32 1
10 s
0.2 – 120 s
0.1
Block 32 1
Block 32_1 From Online
Block 32 1
1s
0 - 5000
1
ENERVISTA MII SETUP
HMI
DEFAULT
RANGE
STEP
FUNCTION 32 2
32_2 FUNCTION
FUNCTION 32 2
Enable 32 2
32_2 Enable
Enable 32 2
NO
YES/NO
NA
Trip Enable 32 2
32_2 Trip
Trip Enable 32 2
NO
YES/NO
NA
Power 32 2
32_2 Power Type
Power 32 2
ACTIVE
ACTIVE / REACTIVE /APPARENT NA
Type 32 2
32_2 Minimum/Maximum
Type 32 2
MINIMUM
MINIMUM / MAXIMUM
NA
Direction 32 2
32_2 Forward/Reverse
Direction 32 2
FORWARD
FORWARD / REVERSE
NA
Alarm Level 32 2
32_2 Alarm Level
Alarm Level 32 2
0.05
0.01 - 1.50
0.01
Alarm Delay 32 2
32_2 Alarm Delay
Alarm Delay 32 2
10 s
0.2 – 120 s
0.1
Trip Level 32 2
32_2 Trip Level
Trip Level 32 2
0.05 pu
0.01 - 1.50
0.01
Trip Delay 32 2
32_2 Trip Delay
Trip Delay 32 2
10 s
0.2 – 120 s
0.1
Block 32 2
Block 32_2 From Online
Block 32 2
1s
0 - 5000
1
ENERVISTA MII SETUP
HMI
DEFAULT
RANGE
STEP
FUNCTION 32 3
32_3 FUNCTION
FUNCTION 32 3
Enable 32 3
32_3 Enable
Enable 32 3
NO
YES/NO
NA
Trip Enable 32 3
32_3 Trip
Trip Enable 32 3
NO
YES/NO
NA
Power 32 3
32_3 Power Type
Power 32 3
ACTIVE
ACTIVE / REACTIVE / APPARENT
NA
Type 32 3
32_3 Minimum/Maximum
Type 32 3
MINIMUM
MINIMUM / MAXIMUM
NA
Direction 32 3
32_3 Forward/Reverse
Direction 32 3
FORWARD
FORWARD / REVERSE
NA
Alarm Level 32 3
32_3 Alarm Level
Alarm Level 32 3
0.05
0.01 - 1.50
0.01
Alarm Delay 32 3
32_3 Alarm Delay
Alarm Delay 32 3
10 s
0.2 – 120 s
0.1
Trip Level 32 3
32_3 Trip Level
Trip Level 32 3
0.05 pu
0.01 - 1.50
0.01
Trip Delay 32 3
32_3 Trip Delay
Trip Delay 32 3
10 s
0.2 – 120 s
0.1
Block 32 3
Block 32_3 From Online
Block 32 3
1 s
0 - 5000
1
Содержание Multilin MIWII
Страница 2: ......
Страница 16: ...1 10 MIWII Directional Power Protection System GEK 113308 1 2 ENERVISTA MII SETUP SOFTWARE 1 GETTING STARTED 1 ...
Страница 88: ...4 30 MIWII Directional Power Protection System GEK 113308 4 7 VIEW 4 COMMUNICATIONS 4 ...
Страница 100: ...5 12 MIWII Directional Power Protection System GEK 113308 5 4 TIME SYNCHRONIZATION 5 SETTINGS 5 ...
Страница 116: ...7 8 MIWII Directional Power Protection System GEK 113308 7 2 LOGIC ELEMENTS 7 LOGIC CONFIGURATION 7 ...
Страница 170: ...13 2 MIWII Directional Power Protection System GEK 113308 13 1 MIWII TROUBLESHOOTING GUIDE 13 TROUBLESHOOTING GUIDE 13 ...
Страница 206: ...B 32 MIWII Directional Power Protection System GEK 113308 B 8 MODBUS MAP STATUS APPENDIXB B ...
Страница 212: ...C 6 MIWII Directional Power Protection System GEK 113308 C 1 TRIP CIRCUIT SUPERVISION FOR MII FAMILY RELAYS APPENDIXC C ...