5-4
MIWII Directional Power Protection System
GEK-113308
5.2 MAIN SETTINGS
5 SETTINGS
5
5.2.6 FUNCTION 32 4 (MIWII2000)
5.2.7 FUSE FAILURE(MIWII1000)
ENERVISTA MII SETUP
HMI
DEFAULT
RANGE
STEP
FUNCTION 32 4
32_4 FUNCTION
FUNCTION 32 4
Enable 32 4
32_4 Enable
Enable 32 4
NO
YES/NO
NA
Trip Enable 32 4
32_4 Trip
Trip Enable 32 4
NO
YES/NO
NA
Power 32 4
32_4 Power Type
Power 32 4
ACTIVE
ACTIVE / REACTIVE / APPARENT NA
Type 32 4
32_4 Minimum/Maximum
Type 32 4
MINIMUM
MINIMUM / MAXIMUM
NA
Direction 32 4
32_4 Forward/Reverse
Direction 32 4
FORWARD
FORWARD / REVERSE
0.01
Alarm Level 32 4
32_4 Alarm Level
Alarm Level 32 4
0.05
0.01 - 1.5
0.01
Alarm Delay 32 4 32_4 Alarm Delay
Alarm Delay 32 4
10 s
0.2 – 120 s
0.1
Trip Level 32 4 32_4 Trip Level
Trip Level 32 4
0.05
0.01 – 1.50
0.01
Trip Delay 32 4 32_4 Trip Delay
Trip Delay 32 4
10 s
0.2 – 120 s
0.1
Block 32 4
Block 32_4 From Online
Block 32 4
1s
0 - 5000
1
ENERVISTA MII SETUP
HMI
DEFAULT
RANGE
STEP
FUSE FAILURE FUSE FAILURE FUSE FAILURE
Enable Fuse
Fuse Failure Enable
Enable Fuse
NO
YES/NO
NA
Содержание Multilin MIWII
Страница 2: ......
Страница 16: ...1 10 MIWII Directional Power Protection System GEK 113308 1 2 ENERVISTA MII SETUP SOFTWARE 1 GETTING STARTED 1 ...
Страница 88: ...4 30 MIWII Directional Power Protection System GEK 113308 4 7 VIEW 4 COMMUNICATIONS 4 ...
Страница 100: ...5 12 MIWII Directional Power Protection System GEK 113308 5 4 TIME SYNCHRONIZATION 5 SETTINGS 5 ...
Страница 116: ...7 8 MIWII Directional Power Protection System GEK 113308 7 2 LOGIC ELEMENTS 7 LOGIC CONFIGURATION 7 ...
Страница 170: ...13 2 MIWII Directional Power Protection System GEK 113308 13 1 MIWII TROUBLESHOOTING GUIDE 13 TROUBLESHOOTING GUIDE 13 ...
Страница 206: ...B 32 MIWII Directional Power Protection System GEK 113308 B 8 MODBUS MAP STATUS APPENDIXB B ...
Страница 212: ...C 6 MIWII Directional Power Protection System GEK 113308 C 1 TRIP CIRCUIT SUPERVISION FOR MII FAMILY RELAYS APPENDIXC C ...