6.2 OUTPUTS AND LEDS CONFIGURATION
6 I/0 CONFIGURATION
6
Outputs/LEDs can be configured to be activated by a single element or by a sum of several of them. These elements are
divided into eight groups, besides the
No definition
element. Elements belonging to the same group can be assigned to
the same output/LED. Elements of different groups need to be assigned to different outputs/LEDs
i
.
In order to assign several elements to activate an output/LED, we first activate the
OR
button, next, click on the
I/O
CONFIGURATION
frame and select the desired element group, then choose the desired elements. In order to invert an
element, select the
NOT
button. Finally, click on the
OK
button.
The Output/LED logic can inverted selecting the general
NOT
button. Outputs can be latched, and LEDs can be set to be
fixed or blinking.
Example:If we want to assign a phase differential trip to an output or LED, the output or LED must be programmed with
32_1 trip, 32_2 trip and 32_3 trip elements . To do this, check the OR box in the corresponding Output or LED line (for this
case, Output1 and LED1). Then click on the OR button that appears in the I/O configuration column, select the desired
group (
ELEMENT TRIPS
) and click the I/O configuration box for every element that will be blocked by the input.
If an output or LED has to activate when the relay is not in local mode, select
Local
from the I/O configuration
dropdownlist. The OR button must not be checked.
Elements from different groups cannot be included in an OR type logic.
i.
or select them in different logic diagrams (see logic configuration further on in this chapter and in
Chapter
4. COMMUNICATIONS
) and
then choose the logic diagrams as the elements that will activate the output/LED
Output/LED = NOT LOCAL
Local
Содержание Multilin MIWII
Страница 2: ......
Страница 16: ...1 10 MIWII Directional Power Protection System GEK 113308 1 2 ENERVISTA MII SETUP SOFTWARE 1 GETTING STARTED 1 ...
Страница 88: ...4 30 MIWII Directional Power Protection System GEK 113308 4 7 VIEW 4 COMMUNICATIONS 4 ...
Страница 100: ...5 12 MIWII Directional Power Protection System GEK 113308 5 4 TIME SYNCHRONIZATION 5 SETTINGS 5 ...
Страница 116: ...7 8 MIWII Directional Power Protection System GEK 113308 7 2 LOGIC ELEMENTS 7 LOGIC CONFIGURATION 7 ...
Страница 170: ...13 2 MIWII Directional Power Protection System GEK 113308 13 1 MIWII TROUBLESHOOTING GUIDE 13 TROUBLESHOOTING GUIDE 13 ...
Страница 206: ...B 32 MIWII Directional Power Protection System GEK 113308 B 8 MODBUS MAP STATUS APPENDIXB B ...
Страница 212: ...C 6 MIWII Directional Power Protection System GEK 113308 C 1 TRIP CIRCUIT SUPERVISION FOR MII FAMILY RELAYS APPENDIXC C ...