8 OPTIONS
8.1 OPTIONS GENERAL VIEW
LPS33U_080-100_RPA system_GE_01US
Digital Energy
g
UPS System
F1
F2
F3
F4
UTILITY INPUT
LP33 Series 80 & 100
1
2
3
4
LOAD
RPA
Board
RPA
Board
RPA
Board
RPA
Board
Digital Energy
g
UPS System
Digital Energy
g
UPS System
Digital Energy
g
UPS System
LP33 Series 80 & 100
LP33 Series 80 & 100
LP33 Series 80 & 100
RPA kit
Redundant Parallel Architecture
Allows extending the unit to a parallel system with 2, 3, or 4 units connected on the
same bus, which ensure the highest reliability rate and increase the power
availability without prior investments.
LPS33U_080-
100_Battery c
abinet_0650_
GE_01
Battery System
Digital Energy
LPS33U_080-
100_Battery c
abinet_1215_G
E_01
Battery System
Digital Energy
Additional battery cabinets
For battery with extended backup time.
Dimensions (WxDxH):
25.66” x 31.50” x 75.00” / 650 x 800 x 1905 mm
47.84” x 31.50” x 75.00” / 1215 x 800 x 1905 mm
S
G
T
4000
_c
us
tomer
in
ter
fac
e_02
1
23456789
10
11
16
15
14
13
12
22
21
20
19
18
17
2
1
Customer Interface
The
Customer Interface Card
allows the client the exchange of information
(monitoring and control) with the following interfaces:
-
Serial port
RS232
.
-
6 programmable output channels.
-
2 programmable input channels, of witch one for
GEN-ON
.
-
EPO
(Emergency Power Off).
3-ph SNMP/WEB plug-in adapter
The
“3-ph SNMP/WEB plug-in adapter”
is an Interface to the
Ethernet Network
, and
provides UPS information via the standard
SNMP
protocol (
Simple Network
Management Protocol)
.
The UPS can therefore be managed by a
Network Management System
(NMS)
or by
our applications (for instance
JUMP
), which uses this information to determine the
state of the UPS in order to guarantee safe and orderly shutdown of the server,
when needed.
GE Power Diagnostics
GE Power Diagnostics
is an anytime, anywhere concept in UPS status monitoring
and alarm noti
fi
cation that has been successfully implemented in numerous of
installations supporting up to multi-hundred UPS.
Based on the leading
Intelligent Remote Information System IRIS
all GE UPS types as
well as 3rd party UPS are supported.
Accessing the latest site information via Web and being alerted by Email, SMS or
Fax, it enables the user to make timely decisions in case of changing critical
conditions.
With comprehensive data collection and analysis
IRIS
is not only a remote
monitoring & diagnostics (RM&D) system but, the core of the integrated service
offering
GE Power Diagnostics
.
GE Data Protection
GE Data Protection
software can communicate with the UPS over
RS-232
,
USB
or
SNMP
to receive status information and measurement values of the UPS.
In case of a critical condition (time on battery, remaining battery autonomy time or
low battery) for the load, the software starts a controlled shutdown.
An enhanced alarm management system provides the possibility to start applications,
send messages, and send e-mails for every upcoming or disappearing alarm.