35
Level lll Cycle Programming – C Values
Several Level III program parameters can be adjusted to
fine-tune a conditioners operation for non-standard
applications. Typically these parameters will not need to
be adjusted as the default settings accommodate most
applications. Contact your Water Treatment Professional
before attempting any programming. The parameters are
accessible by pressing and holding the UP and SET buttons
until the display shows a “C” value.
Note:
The control must by in the treated water position
to change settings.
C# Description
Range
Minimum
Increments
Default
Setting
Notes
C1 Backwash
0 – 200
1 Min
14
Flow rate dictated by size of drain line flow
controller
C2 Regenerant Draw
0 – 200
a
1 Min
See Notes
Automatically calculated from resin volume
and salt dosage settings
C3 Slow Rinse
0 – 200
1 Min
See Notes
Automatically calculated from resin volume
and salt dosage settings
C5 Fast Rinse
0 – 200
1 Min
6
Rinses residual regenerant from tank
C8 Regenerant Refill
0 – 200
a
1 Min
See Notes
Automatically calculated from resin volume
and salt dosage settings
a. Only adjustable when the 293 filter valve has been selected.
Содержание Logix 764
Страница 2: ......
Страница 18: ...16 Typical Installation Drawings Figure 19 Twin Tank Multiple Tank ...
Страница 62: ...60 ...
Страница 63: ... Copyright 2007 General Electric Company Printed in USA P N 3020015 Rev A ...