MA-041
–
DGA 900 Plus - Installation & Commissioning Manual - Rev 1.1
4-Mar-22
Page 85 of 99
Figure 10-17: Required files for OLTC commissioning
These files should be stored with the Commissioning Report.
10.3.5
Import Configuration Files to DGA 900 Plus
To complete the commissioning process, import the recently generated configuration
files into the product. Follow these steps to perform the configuration import:
1.
Using the remote HMI from the computer, connect with the DGA 900 Plus and log
in as an Administrator.
2.
Select
Models > OLTC Tap Position Tracking Configuration
.
In the Configuration Import section, click into the circle to select the
TapPositionCalibration.cfg
file, or click-and-drag the
TapPositionCalibration.cfg
file directly from File Explorer into the circle as
shown in Figure 10-18, and wait for the import to complete.
3.
Using the HMI, select
Models > OLTC Motor Torque Configuration
.
In the Configuration Import section, click into the circle to select the
OltcGroups.cfg
file, or click-and-drag the
OltcGroups.cfg
file directly from File
Explorer into the circle as shown in Figure 10-18, and wait for the import to
complete.
4.
Similar to the previous step, click into the circle to select the
OltcRefData.cfg
file,
or click-and-drag the
OltcRefData.cfg
file directly from File Explorer into the circle
as shown in Figure 10-18, and wait for the import to complete.
Figure 10-18: Configuration Import
–
TapPositionCalibration.cfg, OltcGroups.cfg & OltcRefData.cfg
10.3.6
Finalisation