MA-041
–
DGA 900 Plus - Installation & Commissioning Manual - Rev 1.1
4-Mar-22
Page 76 of 99
Figure 10-5: OLTC Motor Torque Total Time (%)
2.
The adjacent box should list
All limits
as shown in Figure 10-6. If not, select the
‘Alerts’ dropdown menu and choose
All limits
.
Figure 10-6: OLTC Motor Torque Total Time (%)
–
Alerts Off
3.
For each Alert, use the slider control to slide the Alert to the
Off
position as shown
Now repeat these steps for all remaining alarms (in the same manner as above):
4.
Select
OLTC Motor Torque In-Rush Time (%)
from the Alarm source dropdown
menu.
5.
The adjacent box should list
All limits
. If not, select the ‘Alerts’ dropdown menu
and choose
All limits
.
6.
For each Alert, use the slider control to slide the Alert to the
Off
position.
7.
Select
OLTC Motor Torque Maximum 1 (%)
from the Alarm source dropdown
menu.
8.
The adjacent box should list
All limits
. If not, select the ‘Alerts’ dropdown menu
and choose
All limits
.
9.
For each Alert, use the slider control to slide the Alert to the
Off
position.
10.
Select
OLTC Motor Torque Maximum 2 (%)
from the Alarm source dropdown
menu.