MA-041
–
DGA 900 Plus - Installation & Commissioning Manual - Rev 1.1
4-Mar-22
Page 25 of 99
The digital inputs for the cooling status and thermal models wiring are shown in Figure 7-2. Digital inputs are polarised, and the positive supply
must be connected to the D+. Maximum current is 25 mA. Maximum voltage is 24 V.
Figure 7-2: Cooling Banks
–
digital inputs (25 mA max & 24 V max)