FP1500 Installation, Configuration and Commissioning Manual
32
With Alert 1, the control unit warns of an alarm
situation. The operator must press
<RECEIVED>
before the Alert 1 time,
otherwise the full alarm is generated.
If the
control unit is on Received within the time,
Alert 2 begins. Alert 2 begins when Alert 1 is
triggered. For this reason, Alarm 2 must be
adjusted to a time longer than Alert 1, to give
the user time to investigate the cause of the
alarm and take the appropriate decisions. If
<RESET>
is not pressed before the Alert 2
time, a full alarm situation is generated.
ZONE
DELAYED MODE
[001] TO [012]
[yes]
3. Once the times have been adjusted for
alerts 1 and 2, the control unit asks which
zones must be used in delayed mode. The
number of indicated zones shall act in
delayed mode or otherwise, depending on
whether [Yes] or [No] is allocated.
4.2.2 Sensitivity
setting
Day mode sensitivity:
[
MAIN MENU]
[# Exit]
1. Configure
4. Connect
7. See
2. Test.
5. Disconnect
3. Time
6. Print
This adjusts the pre-alarm and alarm thresholds of any
detector. Indicating the start and end time, we allocate
new values during periods of the day when we wish to
vary the default thresholds allocated in the factory.
This gives the sensors greater or lower sensitivity
depending on the zone in which they are located and
the activity carried out in the zone in which they act.
Configuration day mode sensitivity
[CONFIGURE]
[# Exit]
1. System
4. System Op.
7. Events
2. See Config. 5. Check Prog.
8. Day Mode
3. Time/Date 6. Power Supply 9. Codes
1. From the main menu, select option 1
<Configure>
and then option 8
<Day mode>
[DAY MODE]
[# Exit]
1. Delayed Mode
2. Sensitivity Mode
2. Select: point
2 <Sensitivity Mode>
and an
information screen appears.
Allow Mode
:
[NO]
Start Time
:
[00:00]
End Time
:
[00:00]
You must choose the functioning mode:
•
NO:
this disables this function. Uses the default
values of the manufacturer
•
YES:
The control unit asks for the start and end
time of the mode. To change the times, press
< 9
>
, introduce the new values and press
<Enter>
N.B.
If the parameters “Start time” and “End time” are
left at [00:00] they shall be enabled 24 hours.
The alarm levels of the sensors may be changed.
(See
section 4.2.2 Changing the Alarm Thresholds).
1