GEK-49822
because of the insufficient range of the variable resistor, it should
necessary to wind up the control spring adjuster more than 30 degrees (one
unwind it more than 90 degrees (three notches) from the factory
never be
notch) or
Test connections for making pickup and time checks on the time over-current unit are
shown in Fig. 22 and 23. Use a source of
volts or greater with good wave form and
constant frequency.
transformers or phantom loads should not be employed in
testing induction relays since their use may cause a distorted wave form. The contact
in the wound shading coil circuit marked D, see internal connection diagram, must be
blocked closed or
for both the pickup test and the time test.
Time Setting
The setting of the time dial determines the length of time the unit requires to
close its contacts when the current reaches a predetermined value. The contacts are
just closed when the dial is set on 0. When the dial is set on
the disk must travel
the maximum amount to close the contacts and therefore this setting gives the maximum
time setting.
The primary adjustment for the time of operation of the unit is made by means of the
time dial.
However, further adjustment is obtained by moving the permanent magnet
along its supporting shelf; moving the magnet toward the disk shaft decreases the time,
while moving it away increases the time.
Be sure the magnet never extends out beyond
the cutout in the disk.
Pickup Test
Use rated frequency for both the pickup and time tests.
Set the relay at the 0.5 time dial position and 2.0 ampere tap. Using the
connection in Fig. 22, the main unit should close its contacts within
percent
tap value current
amps).
Time Test
Set the relay at No. 5 time dial setting and the 2.0 amp tap. Using the test
connection in Fig. 23, apply five times tap current (10.0 amp) to the relay. The relay
should operate within the limits given in Table 12.
TABLE 12
TOC UNIT OPERATING TIME
LIMITS
Time in Seconds
Relay Type
Min.
Midpoint
Max
1.72
1.78
1.83
1.27
1.31
1.35
0 . 8 9
0.92
0.95
*Indicates Revision
16
Содержание IBCG51M
Страница 24: ...GEK 49822 Fig 1 8043458 Type IBCGHM YlA or the 18CG53M in its Case Front View Indicates Revision 24 YlA Relay...
Страница 36: ...L i i I I I I I i I I I I 0 L...
Страница 37: ...6EK 49822 Fig 14 0376A0934 0 Time Characteristic of Dual Polarized Directional Unit of Type IBCG Relay 37...
Страница 38: ...W 49822 Fig 15 088880269 3 Time current Characteristic of Inverse Time Overcurrent Unit 38...
Страница 45: ...GEK 49822 L I I A Or GLl FR a L Fig 22 D195A9179 0 Test Connections for Checking Pickup of TDC Unit 45...