GEK-49822
CONNECTIONS
l
The internal connection diagrams for the various relays are shown in Fig. 5 to
Typical external wiring diagrams are shown by Fig. 10, 11 and 12.
Unless mounted on a steel panel which adequately grounds the relay case, it is
recommended that the case be grounded through a mounting stud or screw with a conductor
not less than
B&S gage copper wire or its equivalent.
INSPECTION
At the time of installation, the relay should be inspected for tarnished contacts,
loose screws, or other imperfections. If any trouble is found, it should be corrected
in the manner described in the section on SERVICING.
CAUTION
Every circuit in the
case has an auxiliary brush.
It is especially
important on current circuits and other circuits with shorting bars that the auxiliary
brush be bent high enough to engage the connecting plug or test plug before the main
brushes do.
This will prevent CT secondary circuits from being opened. Refer to
* Fig. 21.
OPERATION
Before the relay is put into service, it should be given a check to determine that
factory adjustments have not been disturbed. The time dial will be set at zero before
the relay leaves the factory. If the setting has not been changed,
be
to change this setting in order to open the time overcurrent unit contacts.
following tests are suggested:
TARGET AND SEAL-IN UNIT
1.
Make sure that the tap screw is in the desired tap.
2.
Perform pickup and dropout tests as outlined in the
TIME OVERCURRENT UNIT
ACCEPTANCE TEST section.
1.
Set tap screw on desired tap.
Using the test circuit in Fig. 22, apply
approximately twice tap value current until the contacts just close. Reduce the
current until the light in series with the contacts begins to flicker. This value
of current should be within five percent of tap value.
2.
Check the operating time at some multiple of tap value. This multiple of tap
value may be five times tap rating or the maximum fault current for which the
relay must coordinate. The value used is left to the discretion of the user. Use
*
the test circuit shown in Fig. 23.
*Indicates Revision
18
Содержание IBCG51M
Страница 24: ...GEK 49822 Fig 1 8043458 Type IBCGHM YlA or the 18CG53M in its Case Front View Indicates Revision 24 YlA Relay...
Страница 36: ...L i i I I I I I i I I I I 0 L...
Страница 37: ...6EK 49822 Fig 14 0376A0934 0 Time Characteristic of Dual Polarized Directional Unit of Type IBCG Relay 37...
Страница 38: ...W 49822 Fig 15 088880269 3 Time current Characteristic of Inverse Time Overcurrent Unit 38...
Страница 45: ...GEK 49822 L I I A Or GLl FR a L Fig 22 D195A9179 0 Test Connections for Checking Pickup of TDC Unit 45...