Hydran* M2-X Instruction Manual
Page 182
MA-029
Rev. 1.0,
30-Jul-18
5.
Select an appropriate baud rate using the Up and Down arrow keys. The
recommended setting is 115,200 bps for low-noise environments; if
communication problems arise, try again with a lower baud rate. Press Ok
when done. The Hydran M2-X now displays:
6.
On the laptop computer, launch the
BootDownloader.exe
program,
normally stored in the Hydran M2-X installation folder (typically
C:\Program Files\Hydran M2-X
). The
HM2-X Downloader for Boot Mode
screen, shown in Figure F - 1 below is now displayed. Proceed as follows:
•
In
Comm port:
, select the appropriate COM port.
•
In
Baud rate:
, select the same baud rate as in step 6.
•
Click
Browse...
to locate the
CB.APP
file.
•
Click
Download
to start the program upgrade.
Figure F - 1: Upgrading the Embedded Program Using BootDownloader.exe
7.
The Hydran M2-X now displays the screen below. The
HM2-X Downloader
for Boot
Mode screen now displays status messages in the
Status
: area as
well as the progress percentage at the bottom; when the upgrade is
completed, it displays the message
Upgrade Completed
in its
Status
:
area.