Table B - 5: Logging the Values of the Analog Input Alarm Setup Parameters
Configuring the Analog Output(s) (If Used)
1. Configure the optional analog output(s)
[ ]
2. Check the optional analog output(s)
[ ]
1. Manual test of sensor operation is good?
[ ]
Setting the Operation Mode of the Alarm Relays
Set Relay #1 Mode to Normal [ ] Latch [ ] Force On [ ] Force Off [ ]
[ ]
Set Relay #2 Mode to Normal [ ] Latch [ ] Force On [ ] Force Off [ ]
[ ]
Set Relay #2 Mode to Normal [ ] Latch [ ] Force On [ ] Force Off [ ]
[ ]
Set Relay #4 Mode to Normal [ ] Latch [ ] Force On [ ] Force Off [ ]
[ ]
Verifying the Sensor Parameters
1. Gas detector parameters correspond to those on Test Certificate
[ ]
2. Moisture sensor parameters correspond to those on Test Certificate
[ ]
Logging Values of the Service Data
Parameter
Value
Parameter
Value
Service L
Service V
Service I
Service U
Service A
Service F
Table B - 6: Logging the Values of the Service Data
Resetting the Hourly Trend, Daily Trend and Period B
1. Set Hourly Tr. Period to 1 hour
[ ]
2. Set Daily Tr. Period to 1 day
[ ]
3. Set Hydran PPM Period B to 0 hour
[ ]
4. Wait five minutes
[ ]
5. Set the above parameters to their default value (24 hours, 30 days and 24
hours)
[ ]
Fasten the Hydran M2-X
’s cover
[ ]