AF-600 FP / AF-650 GP Drives E9000
Panel mount use with RTXP base adapter

Contactor

Cat. No.

FLA Range

Lug/ Wire 

Size

Torque  

(in-lbs)

Class 10 Class 20

LAR02AJ

RTN1B

NA

0.16-0.26

#14-8 AWG

14-20

LAR25AJ

RTN1C

NA

0.27-0.41

#14-8 AWG

14-20

LAR45AJ

RTN1D

RT12D

0.42-0.65

#14-8 AWG

14-20

RTN1F

RT12F

0.66-1.10

#14-8 AWG

14-20

RTN1G

RT12G

1.11-1.50

#14-8 AWG

14-20

RTN1H

RT12H

1.51-1.90

#14-8 AWG

14-20

RTN1J

RT12J

1.91-2.5

#14-8 AWG

14-20

RTN1K

RT12K

2.51-4.10

#14-8 AWG

14-20

RTN1L

RT12L

4.11-6.3

#14-8 AWG

14-20

RTN1M

RT12M

6.31-8.5

#14-8 AWG

14-20

RTN1N

RT12N

8.51-12.0

#14-8 AWG

14-20

RTN1P

RT12P

12.1-16

#14-8 AWG

14-20

RTN1S

RT12S

16.1-18

#14-8 AWG

14-20

RTN1T

RT12T

18.1-22

#14-8 AWG

14-20

RTN1U

RT12U

22.1-26

#14-8 AWG

14-20

RTN1V

RT12V

26.1-32

#14-8 AWG

14-20

RTN1W

RT12W

32.1-40

#14-8 AWG

14-20

LAR08AJ

RTN2A

NA

11.5-15

#10-3 AWG

50

Mount direct to contactor

Contactor

Cat. No.

FLA Range

Lug/ Wire 

Size

Torque  

(in-lbs)

Class 10 Class 20

LAR08AJ

RTN2B

NA

15.1-19

#10-3 AWG

50

LAR10AJ

RTN2C

NA

19.1-25

#10-3 AWG

50

RTN2D

RT22D

25.1-32

#10-3 AWG

50

RTN2E

RT22E

32.1-43

#10-3 AWG

50

RTN2G

RT22G

43.1-55

#10-3 AWG

50

RTN2H

RT22H

55.1-65

#10-3 AWG

50

RTN2J

RT22H

65.1-82

#10-3 AWG

50

RTN2L

RT22L

82.1-97

#10-1 AWG

50

RTN2M

RT22M

97.1-110

#10-1 AWG

50

KAR08CJ

RTN3B

NA

55-80

#6-250 MCM

275

RTN3C

RT32C

80.1-90

#6-250 MCM

275

RTN3D

RT32D

90.1-120

#6-250 MCM

275

RTN3E

RT32E

120.1-140 #6-250 MCM

275

RTN3F

RT32F

140.1-190 #6-250 MCM

275

KAR95BYWZ

RTN4N

NA*

120-190

#6-350MCM

200

RTN4P

NA*

190.1-280

#6-350MCM

200

RTN4R

NA*

280.1-310

#6-350MCM

200

KAR95BJWZ

RTN4N

NA*

120-190

#6-350 MCM

200

RTN4P

NA*

190.1-280 #6-350 MCM

200

RTN4R

NA*

280.1-310 #6-350 MCM

200

KAR10BYWZ

RTN5A

NA*

120-190

#6-350MCM

375

KAR11BYWZ

RTN5B

NA*

190.1-280

#6-350MCM

375

KAR11BJWZ

RTN5B

NA*

190.1-280 #6-350 MCM

375

KAR12BJWZ

RTN5C

NA*

280.1-400 #6-350 MCM

375

KAR12BYWZ

RTN5C

NA*

280.1-400 #8-500 MCM

375

RTN5D

NA*

400.1-500 #8-500 MCM

375

RTN5E

NA*

500.1-650 #8-500 MCM

375

*

 

Class 30 is available

WZ – Special for Mebane

Содержание Evolution Series E9000

Страница 1: ...EvolutionSeries E9000 Motor Control Centers User Manual DEH 40472 Rev 08 GE Energy Connections...

Страница 2: ...s 16 Removal of Draw out Motor Control Center Units 18 Operating Handles Door Interlocks and Padlocking Provisions 18 Operating Handle 19 Pilot Bracket and Door 20 NEMA 3R Outdoor Enclosure Installati...

Страница 3: ...on information available at the time of its publication While efforts have been made to ensure accuracy the information contained herein does not cover all details or variations in hardware and softw...

Страница 4: ...ng splits Each shipping split is provided with continuous floor sills and a lifting angle Floor sills and lifting angles are field removable Each shipping split includes a continuous non removable mai...

Страница 5: ...rrier For Arc Resistant design uses this same Lexan barrier with additional Metallic dead front barrier The vertical bus either 300A or 600 850 A is connected with two bolts per phase to the main bus...

Страница 6: ...ous bolt sizes and joint types Bolt Size Copper Joints Aluminum Joints lb ft N m lb ft N m 5 16 18 5 9 7 12 6 5 9 9 12 3 8 16 12 16 16 22 10 15 14 20 1 2 13 30 39 41 53 25 35 34 47 5 8 11 65 80 88 108...

Страница 7: ...than the lifting angle or floor sills Use two or more chains or cables to distribute the weight evenly Pinch bars pipe rollers or slings are useful implements for handling equipment but be careful to...

Страница 8: ...urnished by the GE as well as all applicable contract drawings for the particular installation Pay particular attention to the location of units in the motor control center and their relations to exis...

Страница 9: ...Evolution Series E9000 User Manual 8 Indoor Enclosures Elevation and Mounting 30 Deep Sections 600A to 1200A Main Bus Top Conduit Entry 30 Deep Section...

Страница 10: ...t cable entry Note Bottom rear entrance should only be used with full rear accessibility Figure 6A Bottom conduit entrance details for standard 13 inch deep section low bus position Figure 6B Bottom c...

Страница 11: ...of the 13 inch deep section Surface under motor control center base must be of non combustible material unless bottom covers are installed in each vertical section The overall height of the equipment...

Страница 12: ...the section splits For additional gasket material orderpart number245A1888P5 Gaskets Figure 10A Type 12 and Arc Resistant gasket material between section splits NEC Work Space NEC Work Space is defin...

Страница 13: ...e tops of the sections through front or rear flaps as required For Arc Resistant sections with plenum the conduit can be assembled on top of the plenum GE offers an additional pull boxforhigherconduit...

Страница 14: ...e in Chapter 5 Exhaust Fan InstallationforULType 12 Enclosure and Arc Resistant Vented Fan Shields Filter Assembly UL Type 12 Fan Assembly Arc Resistant VFD Fan Shield Figure 16B Exhaust fan for UL Ty...

Страница 15: ...the cable insulation on any sharp edges such as steel work or screws Where access to the rear of the section is available cables can be brought into the space behind the vertical bus and brought forw...

Страница 16: ...ug is provided in each draw out combination starterunitforterminating a motor frame grounding wire For larger starters the lug is mounted on the horizontal ground bus 5 Use cord or plastic ties to sec...

Страница 17: ...cks are mounted on a metal rail located at the bottom of the unit as shown in Figure 22 The terminal block easily slides into position from either side of the mounting rail Figure 22 Mounting the term...

Страница 18: ...sure that all screw terminals are tight all foreign material and packing are removed and the insulating barriers are secure 7 The unit disconnect must be in the OFF position before the unit can be ins...

Страница 19: ...nadvertent contact Failure to observe this precaution can result in serious injury or death 5 Turn the latches at the top and bottom of the unit a quarter turn counterclockwise to release the unit The...

Страница 20: ...Size 5 FVNR 125 36 CAUTION should be used when removing or installing units considerthe weight intable above Two persons may be required orthe assistance of a lifting devices See page 21 for suggested...

Страница 21: ...er Note that the left module right rear cover has a flange that will be underneath the removed covered with it is replaced This provides an overlapping connection in the rear of the two spliced module...

Страница 22: ...Evolution Series E9000 User Manual 21...

Страница 23: ...at operating handles move freely to the TRIP indicating position With the door closed and latched reset each tripped circuit breaker by pushing the operating handle down beyond the OFF position The op...

Страница 24: ...nected during startup 8 Adjust instantaneous settings on magnetic onlycircuit breakers and or fuse sizes and overload heater selectionsto achieve propermotorand branch circuit protection See NEC Artic...

Страница 25: ...hown Figure 38 Adjust the pilot device bracket and extension bubble lip so it enters in between the keeper bracket and inside of the door Figure 39 Close the door completely and turn the 1 4 turn latc...

Страница 26: ...or interlocks for proper operation 10 Check all indicating lights and replace as required 11 If fuse replacement is necessary always install the same type and rating as the fuses furnished with the mo...

Страница 27: ...ables not required for accessories only 4 Remove the toggle holding plate toggle needs to be in the ON position UP 5 Remove the top four screws in top plate holding the breaker assembly not required f...

Страница 28: ...peed GEH 4806 NEMA Size 3 FVR 2 Speed GEH 4807 NEMA Size 4 FVR 2 Speed GEH 4839 NEMA Size 5 FVR 2 Speed GET 6915A Tech Info Contact Appearance Arc Flash Mitigation Units DEI 007 Remote Racking System...

Страница 29: ...keted 1 HG heavy gasketed 2 3R or 12 6 Power supply characteristics Voltage Number of phases Frequency in Hz 7 Control power voltage and frequency in Hz 8 Nameplate designation and title 9 Motor chara...

Страница 30: ...70 C379A 22 6 23 9 C273B 3 71 4 06 C419A 24 0 26 3 C303B 4 07 4 47 C466A 26 4 27 0 C330B 4 48 4 95 C526A Size 2 Standard and Ambient Comp Motor Full Load Amps 3 Ph 3 Heater Heater Number CR123 Motor...

Страница 31: ...f heater full load current multiplied by 1 25 Circuit breaker tripping may be an indication that a fault current has been interrupted To provide continued protection against fire or shock hazard exami...

Страница 32: ...1 C125B 15 3 6 11 2 12 1 C137B 15 3 7 11 2 12 1 C137B 30 LO 2 12 2 13 0 C151B 15 4 8 12 2 13 0 C151B 30 LO 2 13 1 15 5 C163B 30 1 3 15 6 16 8 C180B 30 1 4 16 9 18 0 C198B 30 2 5 18 1 19 7 C214B 30 2 5...

Страница 33: ...9 130 F161C 150 2 6 Size 5 Standard and Ambient Comp Motor Full Load Amps 3 Ph 3 Heater Heater Number CR123 TEC TECL Rating Mag Break Trip Setting Rec Max 106 115 C592A 550 1670 2 6 116 125 C630A 550...

Страница 34: ...8 81 9 27 C104B 15 3 5 9 28 9 99 C113B 20 2 4 10 0 11 1 C125B 20 2 5 11 2 12 1 C137B 20 3 5 12 2 13 0 C151B 20 3 5 13 1 15 5 C163B 20 4 6 15 6 16 8 C180B 25 3 5 16 9 18 0 C198B 25 3 6 18 1 19 7 C214B...

Страница 35: ...4C 150 3 5 93 5 105 0 F118C 150 3 5 106 0 114 0 F133C 150 3 5 115 0 128 0 F149C 150 4 6 129 0 130 0 F161C 150 4 6 Size 4 Standard Motor Full Load Amps 3 Ph 3 Heater Heater Number CR123 SE Rating Plug...

Страница 36: ...with a service factor of 1 0 multiply the motor full load current by 0 9 and use this value to select heaters Overload relay tripping current in 40 C ambient is the minimum value of full load current...

Страница 37: ...20 1 21 5 C228B 601 21 6 22 5 C250B 601 22 6 23 9 C273B 601 24 0 26 3 C303B 601 26 4 27 0 C330B 601 Size 2 Standard and Ambient Comp Motor Full Load Amps 3 Ph 3 Heater Heater Number CR123 Maximum Fuse...

Страница 38: ...70 6 F848B 2501 70 7 76 3 F914B 2751 76 4 88 7 F104C 3001 88 8 93 4 F114C 3501 93 5 105 F118C 3501 106 114 F133C 4001 115 128 F149C 4001 129 131 F161C 4001 132 135 F174C 4001 Size 5 300 15CT Standard...

Страница 39: ...4 78 5 06 C630A ElectronicOverloadforCircuitBreakerandFused Controllers The tripping current is 120 of the dial setting For continuous rated motors with a service factor of 1 15 to 1 25 set the dial...

Страница 40: ...4 0 CR324GXN 400 600 51 65 to 129 9 CR324GXP 51 130 to 270 CR324GXQ 62 130 to 259 9 CR324HXS 600 Class L 1200 1 300 15 CT s 2 800 5 CT s IECStyleOverloadRelays C2000ContactorCLNCJTypeRTOverloadRelayfo...

Страница 41: ...r Cat No FLA Range Lug Wire Size Torque in lbs Class 10 Class 20 LAR08AJ RTN2B NA 15 1 19 10 3 AWG 50 LAR10AJ RTN2C NA 19 1 25 10 3 AWG 50 RTN2D RT22D 25 1 32 10 3 AWG 50 RTN2E RT22E 32 1 43 10 3 AWG...

Страница 42: ...Evolution Series E9000 User Manual 41 Notes...

Страница 43: ...42 Evolution Series E9000 User Manual Notes...

Страница 44: ...eneral Electric Company 2017 General Electric Company Information provided is subject to change without notice All values are design or typical values when measured under laboratory conditions DEH 404...

Отзывы: