Size 5 – 300:15 CT (Standard and Ambient Comp.)
Motor Full-
Load Amps
3-Ph, 3 Heater
Heater
Number
CR123
SG
Rating
Plug
Instantaneous
Trip Setting
Rec.
Max.
106-115
C592A
250
LO
3
116-125
C630A
250
LO
4
126-135
C695A
250
2
4
136-151
C778A
250
2
5
152-164
C867A
300
2
4
165-179
C955A
300
2
5
180-195
C104B
350
2
4
196-215
C113B
350
2
5
216-231
C125B
400
2
4
232-255
C137B
400
2
5
256-270
C151B
400
3
5
Size 6 – 600:5 CT (Standard and Ambient Comp.)
Motor Full-
Load Amps
3-Ph, 3 Heater
Heater
Number
CR123
SG
Rating
Plug
Instantaneous
Trip Setting
Rec.
Max.
181-197
C220A
400
MIN.
4
198-214
C239A
400
2
5
215-238
C268A
500
MIN
4
239-258
C301A
500
MIN
4
259-290
C326A
500
2
5
291-346
C356A
600
MIN
5
347-387
C379A
600
2
5
388-424
C419A
600
3
MAX
Size 6 – 600:5 CT (Standard and Ambient Comp.)
Motor Full-
Load Amps
3-Ph, 3 Heater
Heater
Number
CR123
SK
Rating
Plug
Instantaneous
Trip Setting
Rec.
Max.
181-197
C220A
400
LO
4
198-214
C239A
400
2
4
215-238
C268A
400
3
5
239-258
C301A
500
LO
4
259-290
C326A
500
2
5
291-346
C356A
800
LO
4
347-387
C379A
800
LO
5
388-423
C419A
800
2
5
424-467
C466A
1000
LO
4
468-516
C526A
1000
2
4
517-540
C592A
1000
2
5
Heaters for Fused Controllers
For continuous-rated motors with a service factor of
1.15 to 1.25, select the appropriate heaters for the
motor full-load current. For continuous-rated motors
with a service factor of 1.0, multiply the motor full-load
current by 0.9 and use this value to select heaters.
Overload relay tripping current in 40° C ambient is the
minimum value of full-load current multiplied by 1.25.
Overload relays with automatic reset may
automatically start a motor connected to a two-wire
control circuit. When automatic restarting is not
desired, use a three-wire control circuit.
Provide short-circuit protection in accordance with the
National Electrical Code, except that fuses are not to
exceed the value shown in the table.
Suitable for use in a circuit capable of delivering not
more than the maximum RMS symmetrical amperes
indicated in the Maximum Fuse and Short-Circuit Rat-
ing table below, 600 V maximum, when protected by an
appropriate fuse having an interrupting rating not less
than the available short-circuit current.
Opening of the fuse(s) may be an indication that
a fault current has been interrupted. To provide
continued protection against fire or shock hazard,
examine all current-carrying parts and other
components of the motor controller and replace
any damaged components. If heater burnout occurs,
the complete overload relay must be replaced.
Maximum Fuse and Short-Circuit Rating
NEMA
Size
Class RK Fuse
Class J Fuse
Class K-1, K-5 Fuse
Max.
Clip
Max. RMS
Sym. Amps
Max.
Clip
Max. RMS
Sym. Amps
Max.
Clip
Max. RMS
Sym. Amps
1
30A
100,000
60A
100,000
Fuse per
Overload
Heater
Table
5,000
2
60
100,000
100
100,000
5,000
3
100
100,000
200
100,000
5,000
4
200
100,000
400
100,000
10,000
5
400
100,000
600
100,000
10,000