37
37
Size 3 (Ambient Comp.)
Motor Full-
Load Amps
3-Ph, 3 Heater
Heater
Number
CR123
Maximum
Fuse
Rating
17.8-18.4
F233B
70
18.5-21.1
F243B
80
21.2-22.1
F270B
80
22.2-26.1
F300B
90
26.2-28.0
F327B
100
28.1-31.3
F357B
110
1
31.4-33.3
F395B
125
1
33.4-34.3
F430B
125
1
34.4-40.9
F487B
150
1
41.0-44.7
F567B
150
1
44.8-51.0
F614B
175
1
51.1-52.0
F658B
200
1
52.1-55.4
F719B
200
1
55.5-63.3
F772B
200
1
63.4-66.1
F848B
200
1
66.2-73.5
F914B
200
1
73.6-82.2
F104C
200
1
82.3-90.0
F114C
200
1
Size 1 (Standard and Ambient Comp.)
Motor Full-
Load Amps
3-Ph, 3 Heater
Heater
Number
CR123
Maximum
Fuse
Rating
27.1-32.2
F357B
110
32.3-34.0
F395B
125
34.1-36.8
F430B
125
36.9-44.6
F487B
150
44.7-48.4
F567B
175
48.5-53.9
F614B
175
54.0-57.4
F658B
200
57.5-60.0
F719B
225
1
60.1-69.5
F772B
225
1
69.6-71.7
F848B
250
1
71.8-79.9
F914B
275
1
80.0-92.3
F104C
300
1
92.4-97.0
F114C
350
1
97.1-108
F118C
400
1
109-118
F133C
400
1
119-131
F149C
400
1
132-135
F161C
400
1
Size 3 (Ambient Comp.)
Motor Full-
Load Amps
3-Ph, 3 Heater
Heater
Number
CR123
Maximum
Fuse
Rating
28.8-32.0
F357B
110
32.1-34.2
F395B
125
34.3-36.7
F430B
125
36.8-43.9
F487B
150
44.0-46.6
F567B
175
46.7-52.6
F614B
175
52.7-55.6
F658B
200
55.7-58.7
F719B
225
1
58.8-67.1
F772B
225
1
67.2-70.6
F848B
250
1
70.7-76.3
F914B
275
1
76.4-88.7
F104C
300
1
88.8-93.4
F114C
350
1
93.5-105
F118C
350
1
106-114
F133C
400
1
115-128
F149C
400
1
129-131
F161C
400
1
132-135
F174C
400
1
Size 5 – 300:15CT (Standard and Ambient Comp.)
Motor Full-
Load Amps
3-Ph, 3 Heater
Heater
Number
CR123
Maximum
Fuse
Rating
109-118
C592A
600
119-128
C630A
600
129-138
C695A
600
139-155
C778A
600
156-168
C867A
600
169-184
C955A
600
185-200
C104B
600
201-221
C113B
600
222-237
C125B
600
238-262
C137B
600
263-270
C151B
600
Electronic Overload Table for Fusible Controllers
Tripping current is 120% of Dial setting. Motors with 1.15-1.25 service
factor, set dial to motor FLA Motors with 1.0 service factor, set dial to
0.9 motor FLA.
NEMA Size FLA Range in Amps Catalog Number Max. Fuse in Amps
1
0.8 to 1.59
CR324CXD
Class R 30 Class J 60
1
1.6 to 3.19
CR324CXE
1
3.2 to 6.49
CR324CXF
1
6.5 to 12.8
CR324CXG
1
13 to 27
CR324CXH
2
13 to 25.6
CR324DXG
60
100
2
26 to 49.9
CR324DXH
2
50 to 100
CR324DXJ
3
17 to 34.9
CR324FXK
100
200
3
35 to 64.9
CR324FXL
3
65 to 90
CR324FXM
4
17 to 34.9
CR324FXK
200
400
4
35 to 64.9
CR324FXL
4
65 to 135
CR324FXM
5
1
32 to 64.0
CR324GXN
400
600
5
1
65 to 129.9
CR324GXP
5
1
130 to 270
CR324GXQ
6
2
130 to 259.9
CR324HXS
600
Class L 1200
6
2
260 to 540
CR324HXT
1
300:15 CT’s
2
800:5 CT’s
Additional motor overload protection required
for MM200 abd MM300 relay applications with
FLA less than 6A.
1
See maximum fuse and short-circuit rating table on page 29