GEEP-124-I  Horizontal Induction Motor

WPI, Antifriction Bearing

The insulation resistance should be measured and

recorded during each inspection of the winding. Refer to
the section entitled Insulation Resistance on page 15. If
the measured value of insulation resistance in megohms
is less than (KV + 1), when corrected to 40C, the
machine should not be put back into service until steps
have been successfully taken on the winding to restore
its insulation resistance to that value, or more. At this
point, a polarization index measurement may also be
helpful as additional data on the condition of the
winding. See the information on page 16 - Polarization
Index.

Moisture and dirt are the two primary causes of

low insulation resistance of a winding. Accordingly, the
first two steps in correcting such a condition are to dry
the winding and to remove all possible dirt and
contamination. Space heaters should always be turned
on when the machine is shut down. If this is not done,
the insulation resistance will usually decrease because of
condensation on the windings. Space heaters may be
used to dry out a winding, but adequate time must be
allowed to accomplish it. Also, low voltage may be
applied across the winding terminals (ac or dc) to
circulate a fraction of must be monitored in order to keep
the temperature below rated during the drying out
process. Six to eight hours, depending upon the size of
the unit, are required for drying a winding with
circulating current. The winding should be thoroughly
cleaned, in order to remove dirt and contamination, as
an important part of the program to increase the
insulation resistance value.

A thorough cleaning and drying program will

usually restore the winding  insulation  resistance  to
(KV + 1) megohms, or more, corrected to 40C. If it does
not, it is probable that some additional factor, beyond
moisture and dirt, exists. If the incoming cable was not
disconnected from the motor leads in the conduit box,
the additional cable could significantly affect the
insulation resistance. Surge capacitors which are directly
connect to the stator winding could procedure a similar
affect. In both cases, the connection with the stator
winding should be opened and the insulation resistance
test repeated.

If all the above corrective actions fail to restore

the insulation resistance value, it is highly probable that
expert Assistance will be required. It is recommended
that a General Electric Service Shop be contacted for
assistance.

There are additional tests which are available for

use on stator windings, particularly on older windings,
to determine their present condition and serviceability.
Among these are high potential dc and ac testing. It is
important that such testing be done only by people
trained in conducting the tests, to avoid unnecessarily
damaging the winding, to correctly interpret the results
and to observe all the safety precautions necessary to
protect personnel. If it is desired to do such testing at
some point in the history of the unit, it is recommended
that a General Electric Service Shop be contacted.

DLCGEEP-124-I/000, Approved, 2016-11-11, CampinasDM

Содержание Custom 8000

Страница 1: ...or should particular problems arise which are not covered sufficiently for the purchaser s purposes the matter should be referred to GE Industrial Control Systems Custom 8000 is a registered trademar...

Страница 2: ...Storage 5 Installation 7 Alignment and Coupling 9 Wiring and Grounding 11 Operation General 13 Maintenance General 19 Maintenance Grease Recommendation 23 Maintenance Drive End Bearing 25 Maintenance...

Страница 3: ...to machinery with high noise levels use proper care and procedures in handling lifting installing operating and maintaining the equipment before operating replace any covers that have been removed for...

Страница 4: ...following National Electrical Manufacturers Association 2101 Street N W Washington DC 20037 American National Standards Institute 1430 Broadway New York NY 10018 Attention Sales Department The Institu...

Страница 5: ...SONNEL OR BOTH Always lift or move the unit with all assembly bolts screws and studs in place secured with the shaft clamp in position when supplied supplied on machines with sleeve bearings only Mach...

Страница 6: ...storage must be protected from moisture condensation on the windings and other critical parts To prevent condensation energize the machine s space heaters to keep the machine temperature above the ro...

Страница 7: ...F SUPPLIED SHOULD NOT EXCEED 80 PERCENT OF THE IGNITION TEMPERATURE REFER TO FACTORY FOR INFORMATION ON SURFACE TEMPERATURE DUST AND OR LINT SHOULD NOT BE ALLOWED TO BUILD UP AROUND THE SURFACE OF THE...

Страница 8: ...be firmly attached to the foundation to withstand the applied torques and normal vibration forces It is also imperative that they be supported evenly on the foundation and be located in a level plane...

Страница 9: ...nufacturer If a machined vertical surface is not accessible on one or both coupling halves feeler or block gauges may be substituted for the two dial indicators in performing the angular alignment che...

Страница 10: ...Fig 2 Mark the locations of the indicating button with a visible mark Set the two dial indicators to zero Then with each coupling a full end float rotate the two coupling halves in 90 degree increment...

Страница 11: ...5 This check may prevent having to break the electrical connections later The stator winding leads are terminated with connectors for bolting to corresponding connectors on the cable from the owner s...

Страница 12: ...ide of the accessory terminal box cover This gasketed cover should be kept closed to prevent the entrance of moisture dust and conducting particles The gasketed cover should be kept closed to prevent...

Страница 13: ...sulting unbalance in currents will in general be significant For example the locked rotor current will be unbalanced by the same percentage as the voltage but at operating speed the percentage unbalan...

Страница 14: ...RESULT IN INJURY TO PERSONNEL Insulation resistance is determined by applying a dc voltage typically 500 or 1000 Volts across insulation measuring the current flow after the voltage has been applied f...

Страница 15: ...oubling the insulation resistance for each 10C reduction in temperature for conditions above the dew point It has been found to be reasonable for new windings The polarization index is frequently help...

Страница 16: ...red Initial test run The starting current of a motor is several times the rated current This starting current causes the windings to heat at a much higher rate than normal and causes the windings to h...

Страница 17: ...nce with NEMA Standard MG 1 20 52 and MG 1 20 53 to be within the following limits unless otherwise specified in the sales contract Speed RPM Maximum Peak to Peak Amplitude Inches on Bearing Housing M...

Страница 18: ...rent forces on the winding end turns are many times greater than the normal condition For the above reasons the frequency of starts and the magnitude of rotational inertia of the connected load must b...

Страница 19: ...repairs in the course of its life it is recommended that they be done in a General Electric Service Shop WARNING BEFORE INITIATING MAINTENANCE PROCEDURES DISCONNECT ALL POWER SOURCES TO MACHINES AND A...

Страница 20: ...n will vary with the item being inspected and with the severity of local environmental conditions Certain items such as winding temperature bearing temperature and vibration amplitude should be monito...

Страница 21: ...ndicate its general condition and allows room for cleaning with a flexible vacuum hose When the rotor is removed on a less frequent schedule more of the winding is accessible For a routine inspection...

Страница 22: ...are required for drying a winding with circulating current The winding should be thoroughly cleaned in order to remove dirt and contamination as an important part of the program to increase the insul...

Страница 23: ...located on the outboard side of the end shield at the bottom of the bearing housing and make certain that the grease relief hole is free of hardened grease The grease fitting is located at the end of...

Страница 24: ...hing liquid through the housing while the machine is operating Flush until no grease comes out with the liquid For flushing use hot mineral oil not more than 100 C or 212 F 4 Continue the cleaning by...

Страница 25: ...though high quality design and workman ship are incorporated in a bearing it sometimes becomes necessary to remove if for maintenance It is for this reason that the following instructions are include...

Страница 26: ...th Reassembly of the bearing should be performed in the following manner 1 Inspect the bearing housing and related parts for foreign material Clean if necessary 2 The machined fits and critical surfac...

Страница 27: ...acement Even though high quality design and workman ship are incorporated in a bearing it sometimes becomes necessary to remove if for maintenance It is for this reason that the following instructions...

Страница 28: ...hould be performed in the following manner 1 Inspect the bearing housing and related parts for foreign material Clean if necessary 2 The machined fits and critical surfaces of the end shield bearing h...

Страница 29: ...IS RECOMMENDED TROUBLE SHOOTING CHART Trouble Possible Cause Action Motor will not start Power not connected Connect power to control and control to motor Check contacts Low Voltage Check motor namepl...

Страница 30: ...e Overheating Overloaded Measure loading with ammeter and compare with full load current on nameplate Reduce load Electrical load unbalance Check for voltage unbalance or single phasing Restricted ven...

Страница 31: ...nd up or damaged Replace seals Bearings Noisy or Vibrating Defective bearings or rough journal Replace bearings or resurface shaft antifriction type Wrong grade of grease Remove old grease and relubri...

Страница 32: ...t and repair Synchronous generator Failure of the machine to Wrong connections Check stator rotor and exciter connections check regulator wiring produce rated output Open circuits Test by ring out cir...

Страница 33: ...al Induction Motor WPI Antifriction Bearing BOLT TIGHTENING REFERENCE Bolt size Torque in LB FT Dry Lubricated 1 4 20 8 7 5 16 18 17 14 3 8 16 30 23 7 16 14 50 38 1 2 13 75 56 5 8 11 150 112 3 4 10 26...

Страница 34: ...sential parts which may deteriorate at an unpredictable rate over a period of time for which the mode of failure is more subtle Air filters used to remove dirt should be inspected and cleaned periodic...

Страница 35: ...al Application or Multiple Units Full Protection one set of each item as originally supplied First Seven Items in 1 as applicable Rotor Stator Exciter Rotor Exciter Stator Synchronous Machines only Re...

Страница 36: ...relative location of the drive motor and driven equipment should permit belt or chain tightening or loosening The belt sheave gear sprocket should be mounted as close to the motor end shield as reaso...

Страница 37: ...nstruction which permits easy maintenance without sacrificing strength or rigidity These motors have received special inspection during the manufacturing and assembly operations to assure that all par...

Страница 38: ...Bearing Cap 19 Bearing Insulation 20 Antifriction Bearing 21 Cover 22 Bearing Locknut Assembly 23 End Shield Gasket when used 24 Upper Half End Shield 25 Air Deflector 26 Fan 27 Dowel Pin 28 Heater F...

Страница 39: ...the stator core where it is directed upward into the top cover In a dripproof machine cooling air enters the frame through openings in the end shields The air is then directed by the air deflectors in...

Страница 40: ...mental laminations punched from magnetic silicon steel The punchings are accurately positioned and stacked to maintain a true stator bore The core is build up axially with packets of punchings separat...

Страница 41: ...GE Industrial Control Systems GEEP 124 I Fort Wayne Indiana46802 41 DLCGEEP 124 I 000 Approved 2016 11 11 CampinasDM...

Отзывы: