3300/25 Dual Accelerometer Input Monitor Operation Manual
28
13. Test Alarms
Use this procedure to test the alarm setpoints that you set in the Alarm Setpoint
Procedure Section. The test uses a function generator to exceed the setpoint levels so
that you can verify that the appropriate LEDs come on.
Use this procedure to test the alarms for both channels.
Testing the channel alarms involves these main steps:
•
Connect and adjust the test instruments
•
Test the Alert setpoint level
•
Test the Danger setpoint level
•
Prepare to bring the monitor on line
NOTE: If your monitor is configured for a single transducer input then you should bypass
the channel which is not under test
(see Section 11)
so that you can verify that the
channel under test is controlling the relays. Be sure to remove Channel Bypass at
the end of this procedure.