Section 10 - Alarm Setpoint Adjustment
25
10. Alarm Setpoint Adjustment
Setpoints cannot be adjusted if trip multiply is installed and active. Trip multiply is active
when the trip multiply contacts are closed.
1. Open the front panel by loosening the two monitor retaining screws and sliding the
front panel to the right.
2. Select the channel to be adjusted by setting either switch
AA
(Adjust channel
A
) or
AB
(Adjust channel
B
) to the left (ON). The selected bargraph will start flashing.
3. To adjust the Alert or Danger setpoints, press and
hold the
ALERT
or
DANGER
button on front panel and
then press the (
↑
) or (
↓
) buttons on the System
Monitor to adjust setpoint value up or down.
4. Reset the selected channel adjust
AA
or
AB
switches
to the right (OFF).
NOTE:
The monitor responds to the previous
setpoint until the option adjust switch is turned off.
Содержание Bently Nevada 3300/25
Страница 11: ...Section 2 Monitor Functions 5 ...
Страница 51: ...Section 16 Self Test 45 When you press the RESET switch on the System Monitor the OK LEDs will stop flashing ...
Страница 93: ...Section 20 Appendix C Filter Board Options PWA 148921 01 87 20 2 Filter Board Jumper Locations ...