
6 Protection Functions
P50 Agile P153
6-10
P153/EN M/B
The fact that both EF1 and EF2 elements may be enabled at the same time leads to a number of
application advantages.
2.4.2
Earth Fault Protection Logic
The Earth Fault current is compared with a set threshold (
IN1>
(n)
Current Set
) for each stage. If it
exceeds this threshold, a Start signal is triggered, provided there are no blocks.
Earth Fault protection can follow the same IDMT characteristics as described in the Overcurrent
Protection Principles section. Please refer to this section for details of IDMT characteristics.
The description also applies to the Earth Fault 2 element (IN2).
The Earth Fault protection trip signal can be blocked by:
•
The Second Harmonic blocking function which is for all three phases. The blocking of Earth
Fault 1 is activated by setting the
IN1> (n) 2H Blocking
cell to ‘Enabled’ and blocking of Earth
Fault 2 is activated by setting the
IN2> (n) 2H Blocking
cell to ‘Enabled’, where (n) is the
number of the stage.
•
User defined blocking logic using ‘IO Mask’ functionality.
2.5
Thermal Overload Function
The heat generated within an item of plant, such as a cable or a transformer, is the resistive loss
(I
2
Rt). The thermal time characteristic is therefore based on the square of the current integrated over
time. The device automatically uses the largest phase current for input to the thermal model.
The equipment is designed to operate continuously at a temperature corresponding to its full load
rating, where the heat generated is balanced with heat dissipated. Over-temperature conditions occur
when currents in excess of their maximum rating are allowed to flow for a period of time. It is known
that temperature changes during heating follow exponential time constants.
The device provides single time constant characteristic which is used to protect cables, dry type
transformers (e.g. type AN), and capacitor banks.
Thermal overload protection is designed to prevent the electrical equipment when operating
temperature is exceeded the maximum designed temperature. The fundamental currents are
measured and analysed to monitor the thermal state. In case of thermal overload function the
calculation of the Time to Trip is given by:
t =
τ
ln ((K²- A)/ (K²- Th. Trip))
Where:
t:
Time to trip (in seconds)
τ
:
Thermal time constant (Te, in seconds) of the equipment to be protected
K:
Thermal overload equal to (I
rms
/ k* IFLA)
Where:
I
rms
:
RMS current corresponding to the largest phase current
IFLA:
Thermal Trip or full load current rating (settable)
k :
Settable (1 to 1.5 step 0.01)
A:
Initial thermal state. If the initial thermal state is 50% then A =0.5
Th. Trip:
Trip thermal state. If the trip thermal state is set at 100%, then Th. Trip is 1
The calculation of the thermal state is given by the following formula:
Содержание Agile P50 Series
Страница 3: ...P50 Agile P153 1 Introduction P153 EN M B 1 1 INTRODUCTION CHAPTER 1...
Страница 4: ...1 Introduction P50 Agile P153 1 2 P153 EN M B...
Страница 10: ...1 Introduction P50 Agile P153 1 8 P153 EN M B...
Страница 11: ...P50 Agile P153 2 Safety Information P153 EN M A 2 1 SAFETY INFORMATION CHAPTER 2...
Страница 22: ...Chapter 2 Safety Information P50 Agile P153 2 12 P153 EN M A...
Страница 23: ...P50 Agile P153 3 Hardware Design P153 EN M B 3 1 HARDWARE DESIGN CHAPTER 3...
Страница 24: ...3 Hardware Design P50 Agile P153 3 2 P153 EN M B...
Страница 32: ...3 Hardware Design P50 Agile P153 3 10 P153 EN M B...
Страница 33: ...P50 Agile P153 4 Front Panel P153 EN M B 4 1 FRONT PANEL CHAPTER 4...
Страница 34: ...4 Front Panel P50 Agile P153 4 2 P153 EN M B...
Страница 39: ...P50 Agile P153 5 Configuration P153 EN M B 5 1 CONFIGURATION CHAPTER 5...
Страница 40: ...P50 Agile P153 5 Configuration P153 EN M B 5 2...
Страница 150: ...P50 Agile P153 5 Configuration P153 EN M B 5 112...
Страница 151: ...P50 Agile P153 6 Protection Functions P153 EN M B 6 1 PROTECTION FUNCTIONS CHAPTER 6...
Страница 152: ...6 Protection Functions P50 Agile P153 6 2 P153 EN M B...
Страница 167: ...P50 Agile P153 7 Protection Parameter Settings P153 EN M B 7 1 PROTECTION PARAMETER SETTINGS CHAPTER 7...
Страница 168: ...7 Protection Parameter Settings P50 Agile P153 7 2 P153 EN M B...
Страница 189: ...P50 Agile P153 8 Monitoring Control P153 EN M B 8 1 MONITORING CONTROL CHAPTER 8...
Страница 190: ...8 Monitoring Control P50 Agile P153 8 2 P153 EN M B...
Страница 207: ...P50 Agile P153 9 SCADA Communications P153 EN M B 9 1 SCADA COMMUNICATIONS CHAPTER 9...
Страница 208: ...12 SCADA Communications P50 Agile P153 9 2 P153 EN M B...
Страница 220: ...12 SCADA Communications P50 Agile P153 9 14 P153 EN M B...
Страница 221: ...P50 Agile P153 10 Installation P153 EN M B 10 1 INSTALLATION CHAPTER 10...
Страница 222: ...10 Installation P50 Agile P153 10 2 P153 EN M B...
Страница 232: ...10 Installation P50 Agile P153 10 12 P153 EN M B 2 4 Case dimensions Figure 10 Case dimensions Note All dimensions in mm...
Страница 233: ...P50 Agile P153 13 Commissioning Instructions P153 EN M B 13 1 COMMISSIONING INSTRUCTIONS CHAPTER 11...
Страница 234: ...13 Commissioning Instructions P50 Agile P153 13 2 P153 EN M B...
Страница 241: ...P50 Agile P153 12 Maintenance and Troubleshooting P153 EN M B 12 1 MAINTENANCE AND TROUBLESHOOTING CHAPTER 12...
Страница 242: ...12 Maintenance and Troubleshooting P50 Agile P153 12 2 P153 EN M B...
Страница 250: ...12 Maintenance and Troubleshooting P50 Agile P153 12 10 P153 EN M B...
Страница 251: ...P50 Agile P153 13 Technical Specifications P153 EN M B 13 1 TECHNICAL SPECIFICATIONS CHAPTER 13...
Страница 252: ...13 Technical Specifications P50 Agile P153 13 2 P153 EN M B...
Страница 263: ...P50 Agile P153 14 Wiring Diagrams P153 EN M B 14 1 WIRING DIAGRAMS CHAPTER 14...
Страница 264: ...14 Wiring Diagrams P50 Agile P153 14 2 P153 EN M B...
Страница 266: ...14 Wiring Diagrams P50 Agile P153 14 4 P153 EN M B 2 WIRING DIAGRAM Figure 1 P153 wiring diagram...
Страница 267: ......