Set Preset reference 0 to first preset speed (par. C-05
Multi-step Frequency 1 - 8
[0]) in percentage of Max reference speed (par. F-53
Maximum Reference
). Ex.:
60%
Set preset reference 1 to second preset speed (par. C-05
Multi-step Frequency 1 - 8
[1] Ex.: 0 % (zero).
Set the timer 0 for constant running speed in par. LC-20
Logic Controller Timer
[0]. Ex.: 2 sec.
Set Event 1 in par. LC-51
Logic Controller Event
[1] to
True
[1]
Set Event 2 in par. LC-51
Logic Controller Event
[2] to
On Reference
[4]
Set Event 3 in par. LC-51
Logic Controller Event
[3] to
Time Out 0
[30]
Set Event 4 in par. LC-51
Logic Controller Event
[4] to
False
[0]
Set Action 1 in par. LC-52
Logic Controller Action
[1] to
Select preset 0
[10]
Set Action 2 in par. LC-52
Logic Controller Action
[2] to
Start Timer 0
[29]
Set Action 3 in par. LC-52
Logic Controller Action
[3] to
Select preset 1
[11]
Set Action 4 in par. LC-52
Logic Controller Action
[4] to
No Action
[1]
Set the Logic Controller in par. LC-00
Logic Controller Mode
to ON.
Start / stop command is applied on terminal 18. If stop signal is applied the frequency converter will decel and go into free mode.
AF-600 FP Design Guide
98
5
Содержание AF-600 FP Series
Страница 11: ...AF 600 FP Design Guide 10 2...
Страница 45: ...AF 600 FP Design Guide 44 3...
Страница 51: ...Do not combine low voltage parts and PELV systems AF 600 FP Design Guide 50 3...
Страница 58: ...4 How to Install AF 600 FP Design Guide 57 4...
Страница 95: ...AF 600 FP Design Guide 94 5...
Страница 102: ...5 1 11 Fixed Variable Speed Pump Wiring Diagram AF 600 FP Design Guide 101 5...
Страница 105: ...AF 600 FP Design Guide 104 6...