Surroundings:
Unit Size 1x types
IP 20/Chassis, IP 21kit/Type 1, IP55/Type12
Unit Size 21 and 22 types
IP55/Type12
Unit Size 23 and 24 types
IP20/Chassis
Unit Size 31 and 32 types
IP55/Type 12
Unit Size 33 and 34 types
IP20/Chassis
Unit Size 41, 42, and 51 types
IP21/Type 1, IP54/Type12
Unit Size 43, 44, and 52 types
IP00/Chassis
Unit Size 61/63
IP21, 54/Type1, 12
Unit Size 62/64
IP21, 54/Type1, 12
IP21/Nema 1 kit for all unit sizes 1x, 2x, and 3x
IP21/NEMA 1/on top of enclosure
Vibration test unit size 1x, 2x, 3x
1.0 g
Vibration test unit size 4x, 5x, 6x
0.7 g
Relative humidity
5% - 95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test
class Kd
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at 60 AVM switching mode)
- with derating
max. 50
°
C
1)
- with full output power of typical EFF2 motors (up to 90% output current)
max. 50
°
C
1)
- at full continuous Drive output current
max. 45
°
C
1)
1)
For more information on derating see the AF-600 FP Design Guide, section on Special Conditions.
Minimum ambient temperature during full-scale operation
0 °C
Minimum ambient temperature at reduced performance
- 10 °C
Temperature during storage/transport
-25 - +65/70 °C
Maximum altitude above sea level without derating
1000 m
Maximum altitude above sea level with derating
3000 m
Derating for high altitude, see section on special conditions
EMC standards, Emission
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
See section on special conditions!
Control card performance:
Scan interval
: 5 ms
Control card, USB serial communication:
USB standard
1.1 (Full speed)
USB plug
USB type B “device” plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from protection earth. Use only isolated laptop/PC as connection to the USB connector on
frequency converter or an isolated USB cable/converter.
Protection and Features:
•
Electronic thermal overload motor protection against overload.
•
Temperature monitoring of the heatsink ensures that the frequency converter trips if the temperature reaches 95 °C ± 5°C. An overload temperature
cannot be reset until the temperature of the heatsink is below 70 °C ± 5°C (Guideline - these temperatures may vary for different power sizes, enclosures
etc.). The frequency converter has an auto derating function to avoid it's heatsink reaching 95 deg C.
•
The frequency converter is protected against short-circuits on motor terminals U, V, W.
•
If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
•
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit voltage is too low or too high.
•
The frequency converter is protected against earth faults on motor terminals U, V, W.
AF-600 FP Design Guide
148
7
Содержание AF-600 FP Series
Страница 11: ...AF 600 FP Design Guide 10 2...
Страница 45: ...AF 600 FP Design Guide 44 3...
Страница 51: ...Do not combine low voltage parts and PELV systems AF 600 FP Design Guide 50 3...
Страница 58: ...4 How to Install AF 600 FP Design Guide 57 4...
Страница 95: ...AF 600 FP Design Guide 94 5...
Страница 102: ...5 1 11 Fixed Variable Speed Pump Wiring Diagram AF 600 FP Design Guide 101 5...
Страница 105: ...AF 600 FP Design Guide 104 6...