2.1.2 Caution
The frequency converter DC link capacitors remain charged after power has been disconnected. To avoid an electrical shock hazard, disconnect
the frequency converter from the mains before carrying out maintenance. Wait at least as follows before doing service on the frequency
converter:
Voltage (V)
Min. Waiting Time (Minutes)
4
15
20
30
40
200 - 240
1.1 - 3.7 kW
5.5 - 45 kW
380 - 480
1.1 - 7.5 kW
11 - 90 kW
110 - 250 kW
315 - 1000 kW
525 - 600
1.1 - 7.5 kW
11 - 90 kW
525 - 690
110 - 400 kW
450 - 1200 kW
Be aware that there may be high voltage on the DC link even when the LEDs are turned off.