The thermistor cut-out value is > 3 k
Ω
.
Integrate a thermistor (PTC sensor) in the motor for winding protection.
Motor protection can be implemented using a range of techniques: PTC sen-
sor in motor windings; mechanical thermal switch (Klixon type); or Electronic
Thermal Electronic Thermal Overload.
Using a digital input and 24 V as power supply:
Example: The frequency converter trips when the motor temperature is too
high.
Parameter set-up:
Set par. F-10
Electronic Overload
to
Thermistor Trip
[2]
Set par. F-12
Motor Thermistor Input
to
Digital Input 33
[6]
Using a digital input and 10 V as power supply:
Example: The frequency converter trips when the motor temperature is too
high.
Parameter set-up:
Set par. F-10
Electronic Overload
to
Thermistor Trip
[2]
Set par. F-12
Motor Thermistor Input
to
Digital Input 33
[6]
Using an analog input and 10 V as power supply:
Example: The frequency converter trips when the motor temperature is too
high.
Parameter set-up:
Set par. F-10
Electronic Overload
to
Thermistor Trip
[2]
Set par. F-12
Motor Thermistor Input
to
Analog Input 54
[2]
Do not select a reference source.
Input
Digital/analog
Supply Voltage
Volt
Threshold
Cut-out Values
Digital
24 V
< 6.6 k
Ω
- > 10.8 k
Ω
Digital
10 V
< 800
Ω
- > 2.7 k
Ω
Analog
10 V
< 3.0 k
Ω
- > 3.0 k
Ω
AF-600 FP Design Guide
42
2
Содержание AF-600 FP Series
Страница 11: ...AF 600 FP Design Guide 10 2...
Страница 45: ...AF 600 FP Design Guide 44 3...
Страница 51: ...Do not combine low voltage parts and PELV systems AF 600 FP Design Guide 50 3...
Страница 58: ...4 How to Install AF 600 FP Design Guide 57 4...
Страница 95: ...AF 600 FP Design Guide 94 5...
Страница 102: ...5 1 11 Fixed Variable Speed Pump Wiring Diagram AF 600 FP Design Guide 101 5...
Страница 105: ...AF 600 FP Design Guide 104 6...