Mains Supply 3 x 525 - 690 VAC
Typical Shaft output at 550 V [kW]
250
315
355
Typical Shaft output at 575 V [HP]
350
400
450
Typical Shaft output at 690 V [kW]
315
400
450
Unit
Size
IP21
42
42
51
Unit Size IP54
42
42
51
Unit
Size
IP00
44
44
52
Output current
Continuous
(at 550 V) [A]
360
418
470
Intermittent (60 sec overload)
(at 550 V) [A]
396
460
517
Continuous
(at 575/690 V) [A]
344
400
450
Intermittent (60 sec overload)
(at 575/690 V) [A]
378
440
495
Continuous KVA
(at 550 V) [KVA]
343
398
448
Continuous KVA
(at 575 V) [KVA]
343
398
448
Continuous KVA
(at 690 V) [KVA]
411
478
538
Max. input current
Continuous
(at 550 V ) [A]
355
408
453
Continuous
(at 575 V) [A]
339
390
434
Continuous
(at 690 V) [A]
352
400
434
Max. cable size, mains, motor and
load share [mm
2
(AWG)]
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
4 x 240
(4 x 500 mcm)
Max. external pre-fuses [A]
1
500
550
700
Estimated power loss
at rated max. load [W]
4)
5821
6149
6449
Weight,
Unit Size IP21, IP 54 [kg]
151
165
263
Weight,
Unit Size IP00 [kg]
138
151
221
Efficiency
4)
0.98
Output frequency
0 - 600 Hz
0 - 500 Hz
0 - 500 Hz
Heatsink
overtemp.
trip
110
°
C
110
°
C
85
°
C
Power card ambient trip
60
°
C
60
°
C
68
°
C
AF-600 FP Design Guide
142
7
Содержание AF-600 FP Series
Страница 11: ...AF 600 FP Design Guide 10 2...
Страница 45: ...AF 600 FP Design Guide 44 3...
Страница 51: ...Do not combine low voltage parts and PELV systems AF 600 FP Design Guide 50 3...
Страница 58: ...4 How to Install AF 600 FP Design Guide 57 4...
Страница 95: ...AF 600 FP Design Guide 94 5...
Страница 102: ...5 1 11 Fixed Variable Speed Pump Wiring Diagram AF 600 FP Design Guide 101 5...
Страница 105: ...AF 600 FP Design Guide 104 6...