![GE 60-806-95R-16Z - Security Concord Express System Control... Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/ge/60-806-95r-16z-security-concord-express-system-control/60-806-95r-16z-security-concord-express-system-control_installation-instructions-manual_4006173007.webp)
Special Installation Requirements
2
•
Hardwire Smoke Detector:
System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400, or 2400TH learned into Sen-
sor Group 26 Sentrol (ESL) models 429AT, 521B, or 521BXT learned into sensor group 26
•
Wireless Smoke Sensor 60-506-319.5 or 60-645-95 learned into sensor group 26
•
IMMEDIATE TROUBLE BEEPS set to on
•
UL 98 OPTIONS set to on
•
RECEIVER FAILURE set to on
•
SIREN VERIFY set to on
•
RF TX TIMEOUT set to 4 hours
•
ALARM VERIFY set to off
•
DISABLE TROUBLE BEEPS set to off
UL 1023 & 985 24-Hour Backup
•
For 24-hour backup, the total current draw for all connected devices is limited to 90 mA con-
tinuous using a 4.0 AH battery.
SIA System Requirements
Note
UL requirements take prior-
ity over SIA requirements.
SIA system requirements are the same as those described for a UL Listed Basic System on page
1, plus:
•
If multiple annunciation is required, use Hardwire Siren part no.13-046.
SIA Setting Requirements
The following table describes programming requirements to meet ANSI-SIA CP-01.
The following table describes non-programmable (hard coded) system operation as required to
meet ANSI-SIA CP-01 and is provided only for your reference.
Shortcut
#
Function
Programming
Page Reference
Testing Page
Reference
Default
Setting
Required Setting
0003
SIA False Alarm
Reduction
21
46 On
On
0013
Exit Extension
22
46
On
On
0014
Auto Stay Arming
22
46
On
On
0016
Duress Code
23
46
Disabled
Disabled
02005
Dialer Abort
28
46
On
On
02006
Dialer Abort Delay
28
46
30 Sec.
15-45 sec.
02007
Cancel Message
28
46
On
On
02009
Call Wait Cancel
28
46
Disabled
On if reporting to central station and
customer has call waiting service
0310
Entry Delay
31
46
30 sec.
30-240 sec.
0311
Exit Delay
31
46
60 sec.
45-184 sec.
05014
Swinger Limit
35
46
1
1
0900
Smoke Verify
42
46
Off
On if smoke alarms are programmed
into system
N/A
Cross Zoning
57
46
Disabled
Enabled for zones with a high
probability of false alarms
Function
Operation
Disarm During Entry Delay
Enter Code Only (or 1 + CODE)
Cancel Alarm
Enter Code Only (or 1 + CODE)
Abort Annunciation
Enabled