![GE 60-806-95R-16Z - Security Concord Express System Control... Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/ge/60-806-95r-16z-security-concord-express-system-control/60-806-95r-16z-security-concord-express-system-control_installation-instructions-manual_4006173043.webp)
Programming the Panel
38
The following describes how to program the settings that appear under
SIREN OPTIONS—
PARTITION 1
.
Sensors Menu
Note
If 2-wire smoke detectors
are connected to hardwire
zone input 6, the Two-wire
Smoke setting must be
turned on
before
entering
the
LEARN SENSORS
menu.
See
ONBOARD OPTIONS—
INPUTS
.
The
SENSORS
menu gives you access to the following:
•
LEARN SENSORS
—lets you learn hardwire zones and wireless sensors into panel memory and
assign zones/sensors to specific partitions.
•
SENSOR TEXT
—lets you program sensor text for zone/sensor identification.
•
DELETE SENSORS
—lets you delete zones/sensors from panel memory.
•
EDIT SENSORS
—lets you view and/or change sensor/zone group assignment, view sensor
number and text assignments of learned sensors/zones, identify whether zone is wireless or
hardwire, and indicates sensor/zone/touchpad input N/C or N/O configuration.
The following describes how to program the sensor settings that appear under
LEARN SENSORS
.
Disable Trouble Beeps (0601)
Siren Options-Global (Default=off)
This setting determines whether or not the panel activates trouble beeps when
a wireless device supervisory condition is detected.
Note
For UL Listed systems, this feature must be off.
¾
To turn Disable Trouble Beeps off or on:
1.
With the display showing
DISABLE TR BEEPS
OFF/ON
(current setting)
, press
1
(off) or
2
(on). The display flashes the entered setting.
2.
Press
ƒ
and the display shows the new set-
ting.
UL 98 Options (0602)
Siren Options-Global (Default=off)
This setting determines whether or not the panel complies with UL 98 require-
ments (4-hour trouble beep restart, 4-hour backup battery test, 2-hour supervi-
sory time period for sensor group 26—Fire).
Note
For UL Listed systems, this feature must be on.
¾
To turn UL 98 Options off or on:
1. With the display showing
UL 98 OPTIONS
OFF/ON
(current setting)
, press
1
(off) or
2
(on). The display flashes the entered setting.
2. Press
ƒ
and the display shows the new set-
ting.
Siren Verify (0610)
Siren Options-Partition 1 (Default=off)
This setting determines whether or not the panel monitors sirens connected to
panel terminal 7 (OUT1/+12V).
When this feature is on, sirens connected to panel terminals 3 (GND) and 7
(OUT1/+12V) require a 2k end-of-line resistor. Refer to “Installing the Sys-
tem—Connecting Sirens” for complete details.
Note
For UL Listed systems, this feature must be on.
¾
To turn Siren Verify off or on:
1.
With the display showing
SIREN VERIFY
OFF/ON
(current setting)
, press
1
(off) or
2
(on). The display flashes the entered
setting.
2.
Press
ƒ
and the display shows the new
setting.