6-8
239 Motor Protection Relay
GE Multilin
6 239PC SOFTWARE
6 239PC SOFTWARE
6
3. If 239PC cannot establish communication with the relay, the following message will be displayed.
4. Click on
Yes
to edit the 239PC communication settings. This will display the
COMMUNICATION/
COMPUTER
window shown below.
5. Set
Slave Address
to match the relay address setpoint.
6. Set
Communication Port #
to the COM port where the relay is connected.
7. Set
Baud Rate
to match the relay baud rate setpoint.
8. Set
Parity
to match the relay parity setpoint.
9. If using the GE Multilin F485 converter, leave the
Control Type
setting as is.
10. Set
Startup Mode
to “Communicate with relay”.
11. Click the
ON
button to communicate with the relay and 239PC will notify when communications
have been established with the relay. If it fails to communicate, check the following:
•
Ensure that the settings above match the relay settings.
•
Ensure the COM port setting matches the COM port being used.
•
Ensure the hardware is connected correctly as shown in Figure 6–1: TYPICAL COMMU-
NICATIONS SETUP on page 6–1.
•
Ensure the RS485 cable polarity is correct and connected to the correct relay terminals.
Содержание 239
Страница 2: ......
Страница 4: ......
Страница 16: ...1 10 239 Motor Protection Relay GE Multilin 1 OVERVIEW 1 OVERVIEW 1 ...
Страница 96: ...6 6 239 Motor Protection Relay GE Multilin 6 239PC SOFTWARE 6 239PC SOFTWARE 6 6 5 239PC MENU STRUCTURE ...
Страница 104: ...6 14 239 Motor Protection Relay GE Multilin 6 239PC SOFTWARE 6 239PC SOFTWARE 6 ...
Страница 149: ...GE Multilin 239 Motor Protection Relay 8 9 8 TESTING 8 TESTING 8 Figure 8 2 239 HARDWARE BLOCK DIAGRAM ...
Страница 150: ...8 10 239 Motor Protection Relay GE Multilin 8 TESTING 8 TESTING 8 ...
Страница 152: ...A 2 239 Motor Protection Relay GE Multilin A 1 239 WARRANTY APPENDIX A A ...
Страница 157: ...GE Multilin 239 Motor Protection Relay NOTES ...