239 Motor Protection Relay
GE Multilin
4 PROGRAMMING
4 PROGRAMMING
4
MESSAGE
▼
MESSAGE
▲
| RTD 1
|
RTD 1 APPLICATION:
STATOR
RTD 1 TYPE:
100 PT
RTD 1 TRIP
TEMPERATURE
≥
130 °C
| RTD 2
|
Range: STATOR, BEARING, OFF
Range: 100PT, 100NI, 120NI, 10CU
Range:
0 to 200°C, OFF; step 1°C
0 to 400°F, OFF; step 1°F
RTD 2 APPLICATION:
STATOR
| RTD 3
|
RTD 1 ALARM
TEMPERATURE
≥
110 °C
RTD 2 TYPE:
100 PT
RTD 2 TRIP
TEMPERATURE
≥
90 °C
RTD 3 APPLICATION:
BEARING
RTD 3 TYPE:
100 PT
RTD 3 TRIP
TEMPERATURE
≥
90 °C
SEE NEXT PAGE
SEE NEXT PAGE
MESSAGE
▲
MESSAGE
▲
MESSAGE
▼
MESSAGE
▼
RTD 3 ALARM
TEMPERATURE
≥
75 °C
SEE PREVIOUS PAGE
SEE PREVIOUS PAGE
| RTD SENSOR FAILURE
|
RTD SENSOR FAILURE
ALARM: OFF
MESSAGE
▲
MESSAGE
▼
Range:
0 to 200°C, OFF; step 1°C
0 to 400°F, OFF; step 1°F
RTD 2 ALARM
TEMPERATURE
≥
75 °C
Range: STATOR, BEARING, OFF
Range: 100PT, 100NI, 120NI, 10CU
Range:
0 to 200°C, OFF; step 1°C
0 to 400°F, OFF; step 1°F
Range:
0 to 200°C, OFF; step 1°C
0 to 400°F, OFF; step 1°F
Range: ON, OFF
Range: STATOR, BEARING, OFF
Range: 100PT, 100NI, 120NI, 10CU
Range:
0 to 200°C, OFF; step 1°C
0 to 400°F, OFF; step 1°F
Range:
0 to 200°C, OFF; step 1°C
0 to 400°F, OFF; step 1°F
DESIGNATES SETPOINTS
THAT ARE ONLY VISIBLE IF
RTD OPTION IS INSTALLED
Содержание 239
Страница 2: ......
Страница 4: ......
Страница 16: ...1 10 239 Motor Protection Relay GE Multilin 1 OVERVIEW 1 OVERVIEW 1 ...
Страница 96: ...6 6 239 Motor Protection Relay GE Multilin 6 239PC SOFTWARE 6 239PC SOFTWARE 6 6 5 239PC MENU STRUCTURE ...
Страница 104: ...6 14 239 Motor Protection Relay GE Multilin 6 239PC SOFTWARE 6 239PC SOFTWARE 6 ...
Страница 149: ...GE Multilin 239 Motor Protection Relay 8 9 8 TESTING 8 TESTING 8 Figure 8 2 239 HARDWARE BLOCK DIAGRAM ...
Страница 150: ...8 10 239 Motor Protection Relay GE Multilin 8 TESTING 8 TESTING 8 ...
Страница 152: ...A 2 239 Motor Protection Relay GE Multilin A 1 239 WARRANTY APPENDIX A A ...
Страница 157: ...GE Multilin 239 Motor Protection Relay NOTES ...