4-16
239 Motor Protection Relay
GE Multilin
4 PROGRAMMING
4 PROGRAMMING
4
MESSAGE
▼
MESSAGE
▲
| MECHANICAL JAM
|
MECHANICAL JAM
FUNCTION: OFF
MECHANICAL JAM
PICKUP
≥
2.0 x FLC
MECHANICAL JAM
DELAY: 2 s
| UNDERCURRENT
|
Range: OFF, TRIP, ALARM,
AUXILIARY, TRIP&AUX
Range: 0.1 to 10.0
Step 0.1 x FLC
Range: 0 to 250; Step: 1 s.
UNDERCURRENT
FUNCTION: OFF
| UNBALANCE
|
INHIBIT ON START
FOR: UNLIMITED s
Range: OFF, ALARM, AUXILIARY,
TRIP, ALARM & AUX, TRIP & AUX
Range: 0 to 250; Step: 1 s.
Range: 5 to 100; Step: 1%
UNDERCURRENT
PICKUP
≤
50% FLC
UNDERCURRENT
DELAY: 2 s
Range: 5 to 100; Step: 1%
PHASE UNBALANCE
TRIP: ON
PHASE UNBALANCE
TRIP PICKUP
≥
20 %
PHASE UNBALANCE
TRIP DELAY: 2 s
Range: ON, OFF
Range: 0 to 60; Step: 1 s
Range: 0 to 6000, UNLIMITED
Step: 1 s
SEE NEXT PAGE
SEE NEXT PAGE
MESSAGE
▲
MESSAGE
▲
MESSAGE
▼
MESSAGE
▼
PHASE UNBALANCE
ALARM: ON
PHASE UNBALANCE
ALARM PICKUP
≤
5 %
SEE PREVIOUS PAGE
SEE PREVIOUS PAGE
Range: ON, OFF
Range: 5 to 100
Step: 1%
| HOT MOTOR
|
THERMAL CAPACITY
USED ALARM
≥
OFF %
MESSAGE
▲
MESSAGE
▼
Range: 0 to 100; Step: 1%
Содержание 239
Страница 2: ......
Страница 4: ......
Страница 16: ...1 10 239 Motor Protection Relay GE Multilin 1 OVERVIEW 1 OVERVIEW 1 ...
Страница 96: ...6 6 239 Motor Protection Relay GE Multilin 6 239PC SOFTWARE 6 239PC SOFTWARE 6 6 5 239PC MENU STRUCTURE ...
Страница 104: ...6 14 239 Motor Protection Relay GE Multilin 6 239PC SOFTWARE 6 239PC SOFTWARE 6 ...
Страница 149: ...GE Multilin 239 Motor Protection Relay 8 9 8 TESTING 8 TESTING 8 Figure 8 2 239 HARDWARE BLOCK DIAGRAM ...
Страница 150: ...8 10 239 Motor Protection Relay GE Multilin 8 TESTING 8 TESTING 8 ...
Страница 152: ...A 2 239 Motor Protection Relay GE Multilin A 1 239 WARRANTY APPENDIX A A ...
Страница 157: ...GE Multilin 239 Motor Protection Relay NOTES ...