4-42
239 Motor Protection Relay
GE Multilin
4 PROGRAMMING
4 PROGRAMMING
4
When thermistor simulation is turned on the following flash message will be displayed for 3 sec-
onds.
When thermistor simulation is turned off the following flash message will be displayed for 3 sec-
onds.
•
THERMISTOR RESISTANCE: Enter the value of the thermistor resistance to be simulated. The
functionality of the thermistor remains as is with an actual input connected to the 239.
•
SIMULATION ENABLED FOR: Select the desired length of time that simulation will be enabled.
When the programmed time has elapsed, thermistor simulation will turn off. If
81/,0,7('
is
selected, simulated thermistor input will be used until simulation is turned off via the
6,08/$7,21
212))
setpoint or via the serial port or until control power is removed from the 239.
g) RTD SIMULATION
•
SIMULATION: Enter ON to switch from actual input to the programmed simulation temperature
value of each RTD input value. While simulation is on all three RTD r inputs will be overridden by
the simulated temperature values. Set this setpoint to
2))
after simulation is complete. As a safe-
guard, simulation will automatically turn off if:
•power to the 239 is turned off and on
•time programmed in
6 7(67,1*?57' 6,08/$7,21?6,08/$7,21 (1$%/(' )25
setpoint has
elapsed since simulation was first enabled
When RTD simulation is turned on the following flash message will be displayed for 3 seconds.
When RTD simulation is turned off the following flash message will be displayed for 3 seconds.
•
RTD 1/2/3 TEMPERATURE: Enter the value of the each RTD temperature to be simulated. The
functionality of the RTDs remains as is with actual inputs connected to the 239.
•
SIMULATION ENABLED FOR: Select the desired length of time that simulation will be enabled.
When the programmed time has elapsed, RTD simulation will turn off. If
81/,0,7('
is selected,
simulated RTD input will be used until simulation is turned off via the
6,08/$7,21212))
setpoint
or via the serial port or until control power is removed from the 239.
h) GE MULTILIN USE ONLY
•
SERVICE PASSCODE CODE: These messages are accessed by GE Multilin personnel only for
testing and service.
SIMULATION
HAS BEEN ENABLED
THERMISTOR SIMULATION
HAS BEEN DISABLED
SIMULATION
HAS BEEN ENABLED
RTD SIMULATION
HAS BEEN DISABLED
Содержание 239
Страница 2: ......
Страница 4: ......
Страница 16: ...1 10 239 Motor Protection Relay GE Multilin 1 OVERVIEW 1 OVERVIEW 1 ...
Страница 96: ...6 6 239 Motor Protection Relay GE Multilin 6 239PC SOFTWARE 6 239PC SOFTWARE 6 6 5 239PC MENU STRUCTURE ...
Страница 104: ...6 14 239 Motor Protection Relay GE Multilin 6 239PC SOFTWARE 6 239PC SOFTWARE 6 ...
Страница 149: ...GE Multilin 239 Motor Protection Relay 8 9 8 TESTING 8 TESTING 8 Figure 8 2 239 HARDWARE BLOCK DIAGRAM ...
Страница 150: ...8 10 239 Motor Protection Relay GE Multilin 8 TESTING 8 TESTING 8 ...
Страница 152: ...A 2 239 Motor Protection Relay GE Multilin A 1 239 WARRANTY APPENDIX A A ...
Страница 157: ...GE Multilin 239 Motor Protection Relay NOTES ...