32
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
RS485 INTERFACE (MODBUS RTU)
CHAPTER 1: COMMUNICATIONS GUIDE
40917
0394
Start Inhibit Margin
0
11
1
%
F1
*
11
1
40918
0395
Reserved
---
---
---
---
---
---
1
40919
0396
Starts/Hour Limit
1
6
1
F1
*
6
1
40920
0397
Time Between Starts
1
3601
1
s
F1
*
3601
1
40921
0398
Reserved
---
---
---
---
---
---
1
CHANGE MODE
40922
0399
Change Mode on Comm Alarm 0
1
1
---
FC126
0
1
40923
039A
Change Mode when running
0
1
1
---
FC126
0
1
40924
039B
Reserved
---
---
---
---
---
---
1
40925
039C
Reserved
---
---
---
---
---
---
1
RESTART BLOCK
40926
039D
Restart Block Time
1
50001
1
s
F1
*
50001
1
40927
039E
Reserved
---
---
---
---
---
---
1
▼
▼
▼
▼
▼
▼
▼
▼
▼
▼
40930
03A1
Reserved
1
KW DEMAND
40931
03A2
kW Demand Period
5
90
1
min
F1
15
1
40932
03A3
kW Demand Alarm
0
2
1
FC115
0
1
40933
03A4
Reserved
1
40934
03A5
kW Demand Alarm Level
1
50000
1
kW
F1
100
1
40935
03A6
kW Demand Alarm Events
0
1
1
FC103
0
1
KVAR DEMAND
40936
03A7
kvar Demand Period
5
90
1
min
F1
15
1
40937
03A8
kvar Demand Alarm
0
2
1
FC115
0
1
40938
03A9
Reserved
1
40939
03AA
kvar Demand Alarm Level
1
50000
1
kvar
F1
100
1
40940
03AB
kvar Demand Alarm Events
0
1
1
FC103
0
1
KVA DEMAND
40941
03AC
kVA Demand Period
5
90
1
min
F1
15
1
40942
03AD
kVA Demand Alarm
0
2
1
FC115
0
1
40943
03AE
Reserved
1
40944
03AF
kVA Demand Alarm Level
1
50000
1
kVA
F1
100
1
40945
03B0
kVA Demand Alarm Events
0
1
1
FC103
0
1
TEST OUTPUT
40956
03BB
Force Operation of Relays
0
32
1
F1
0
1
40957
03BC
MCC Last Key Pressed
144
159
1
F1
*
159
1
CALIBRATION
41040
040F
Calibration Date
0
203360302 1
---
F18
0
2
41042
0411
Calibration Time
0
389757795 1
---
F19
0
2
41044
0413
Reserved
---
---
---
---
---
---
1
▼
▼
▼
▼
▼
▼
▼
▼
▼
▼
41105
0450
Reserved
1
SECURITY
41106
0451
Passcode Level 1
11111
55556
1
F1
*
11111
1
41107
0452
Passcode Level 2
11111
55556
1
F1
*
22222
1
41108
0453
Passcode Level 3
11111
55555
1
F1
41532
1
Modbus
Hex
Description
Min
Max
Step
Units
Format Default
Size in