28
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
RS485 INTERFACE (MODBUS RTU)
CHAPTER 1: COMMUNICATIONS GUIDE
40664
0297
Recording of Level Events
0
1
1
---
FC126
1
1
40665
0298
Recording of Dropout Events
0
1
1
---
FC126
1
1
40666
0299
Recording of Set Time/Date
Events
0
1
1
---
FC126
0
1
40667
029A
Event Record Selector
1
65535
1
---
F1
1
1
40668
029B
Reserved
---
---
---
---
---
---
1
▼
▼
▼
▼
▼
▼
▼
▼
▼
▼
40700
02BB
Reserved
1
RESET SETUP
40701
02BC
Reset Lockout Using Reset Key 0
1
0
---
FC126
0
1
THERMAL MODEL SETUP
40702
02BD
Overload Pickup Level
101
125
1
x FLA
F3
101
1
40703
02BE
Unbalance K Factor
0
19
1
---
F1
0
1
40704
02BF
Cool Time Constant Running
1
1000
1
min
F1
15
1
40705
02C0
Cool Time Constant Stopped
1
1000
1
min
F1
30
1
40706
02C1
Hot/Cold Safe Stall Ratio
1
100
1
%
F1
75
1
40707
02C2
Thermal Capacity Alarm Level 10
101
1
%
F1
*
101
1
40708
02C3
Standard Overload Curve
1
15
1
---
F1
4
1
40709
02C4
Reserved
---
---
---
---
---
---
1
40710
02C5
RTD Bias - Minimum T
0
251
1
°C
F1
*
251
1
40711
02C6
RTD Bias - Center T
0
251
1
°C
F1
*
251
1
40712
02C7
RTD Bias - Maximum T
0
251
1
°C
F1
*
251
1
40713
02C8
Minimize Reset Time
0
1
1
---
FC126
0
1
40714
02C9
Overload Reset Mode
0
1
1
---
FC160
1
1
40715
02CA
Reserved
---
---
---
---
---
---
1
40716
02CB
Reserved
---
---
---
---
---
---
1
40717
02CC
Reserved
---
---
---
---
---
---
1
40718
02CD
Reserved
---
---
---
---
---
---
1
MECHANICAL JAM
40719
02CE
Mechanical Jam Level
101
451
1
x FLA
F3
*
451
1
40720
02CF
Mechanical Jam Delay
1
300
1
s
F2
1
1
40721
02D0
Reserved
---
---
---
---
---
---
1
▼
▼
▼
▼
▼
▼
▼
▼
▼
▼
40724
02D3
Reserved
---
---
---
---
---
---
1
RTD TYPES
40725
02D4
Stator RTD Type
0
2
1
FC120
0
1
40726
02D5
Bearing RTD Type
0
2
1
FC120
0
1
40727
02D6
Ambient RTD Type
0
2
1
FC120
0
1
40728
02D7
Other RTD Type
0
2
1
FC120
0
1
RTD OPEN/SHORT CIRCUIT (REQUIRED=IO_G)
40729
02D8
RTD Open/Short Alarm
0
1
1
---
FC126
0
1
40730
02D9
RTD Short Circuit Alarm
0
1
1
FC126
0
1
▼
▼
▼
▼
▼
▼
▼
▼
▼
▼
40734
02DD
Reserved
---
---
---
---
---
---
1
RTD #1 (REQUIRED=IO_G)
40735
02DE
RTD 1 Application
0
4
1
---
FC121
0
1
Modbus
Hex
Description
Min
Max
Step
Units
Format Default
Size in
Words