134
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
FIELDBUS INTERFACE
CHAPTER 1: COMMUNICATIONS GUIDE
8
Vab
Volts
F1
2
9
Vbc
Volts
F1
2
A
Vca
Volts
F1
2
B
Average Line Voltage
Volts
F1
2
C
Van
Volts
F1
2
D
Vbn
Volts
F1
2
E
Vcn
Volts
F1
2
F
Va1 angle
Degree
F1
2
10
Vb1 angle
Degree
F1
2
11
Vc1 angle
Degree
F1
2
12
System Frequency
Hz
F3
2
13
Power factor
None
F21
2
14
Real Power
Kw
F13
4
15
Reactive Power
Kvar
F13
4
16
Apparent Power
Kva
F2
2
17
MWh Consumption
Mwh
F17
4
18
Mvarh Consumption
Mvarh
F17
4
19
Hottest Stator RTD
None
F1
1
1A
Hottest Stator RTD Temp
Deg C
F4
2
1B
RTD 1 Temperature
Deg C
F4
2
1C
RTD 2 Temperature
Deg C
F4
2
1D
RTD 3 Temperature
Deg C
F4
2
1E
RTD 4 Temperature
Deg C
F4
2
1F
RTD 5 Temperature
Deg C
F4
2
20
RTD 6 Temperature
Deg C
F4
2
21
Learned Acceleration Time
Secs
F2
2
22
Learned Starting Current
Amps
F10
4
23
Learned Starting Capacity
%
F1
2
24
Learned Average Motor Load
%FLA
F3
2
25
Number of motor starts
None
F1
2
26
Number of UV Restarts
None
F1
2
27
Motor Running Hours
Hours
F9
4
28
Cause of Last Trip
None
FC134
2
29
Time of Last Trip
None
F19
4
2A
Date of Last Trip
None
F18
4
2B
Phase A Pre Trip Current
Amps
F10
4
2C
Phase B Pre Trip Current
Amps
F10
4
2D
Phase C Pre Trip Current
Amps
F10
4
2E
Pre Trip Ground Current
Amps
F10
4
2F
Pre Trip Motor Load
%
F1
2
30
Pre Trip Current Unbalance
%
F1
2
31
Pre Trip Vab Voltage
Volts
F1
2
32
Pre Trip Vbc Voltage
Volts
F1
2
33
Pre Trip Vca Voltage
Volts
F1
2
0x
Pre Trip Van Voltage
Volts
F1
2
35
Pre Trip Vbn Voltage
Volts
F1
2
ATTRIBUTE NO.
(HEX VALUE)
DESCRIPTION
UNIT
FORMAT
CODE