B-38
C60 Breaker Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
955C
...Repeated for Direct Input/Output 30
9568
...Repeated for Direct Input/Output 31
9574
...Repeated for Direct Input/Output 32
IEC 61850 received integers (read/write setting registers)
9910
IEC61850 GOOSE UInteger 1 default value
0 to 429496295
---
1
F003
1000
9912
IEC61850 GOOSE UInteger input 1 mode
0 to 1
---
1
F491
0 (Default Value)
9913
...Repeated for IEC61850 GOOSE UInteger 2
9916
...Repeated for IEC61850 GOOSE UInteger 3
9919
...Repeated for IEC61850 GOOSE UInteger 4
991C
...Repeated for IEC61850 GOOSE UInteger 5
991F
...Repeated for IEC61850 GOOSE UInteger 6
9922
...Repeated for IEC61850 GOOSE UInteger 7
9925
...Repeated for IEC61850 GOOSE UInteger 8
9928
...Repeated for IEC61850 GOOSE UInteger 9
992B
...Repeated for IEC61850 GOOSE UInteger 10
992E
...Repeated for IEC61850 GOOSE UInteger 11
9931
...Repeated for IEC61850 GOOSE UInteger 12
9934
...Repeated for IEC61850 GOOSE UInteger 13
9937
...Repeated for IEC61850 GOOSE UInteger 14
993A
...Repeated for IEC61850 GOOSE UInteger 15
993D
...Repeated for IEC61850 GOOSE UInteger 16
FlexElement Actuals (Read Only) (16 modules)
9A01
FlexElement™ 1 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A03
FlexElement™ 2 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A05
FlexElement™ 3 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A07
FlexElement™ 4 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A09
FlexElement™ 5 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A0B
FlexElement™ 6 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A0D
FlexElement™ 7 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A0F
FlexElement™ 8 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
Teleprotection Inputs/Outputs (Read/Write Settings)
9B00
Teleprotection Function
0 to 1
---
1
F102
0 (Disabled)
9B01
Teleprotection Number of Terminals
2 to 3
---
1
F001
2
9B02
Teleprotection Number of Channels
1 to 2
---
1
F001
1
9B03
Teleprotection Local Relay ID
0 to 255
---
1
F001
0
9B04
Teleprotection Terminal 1 ID
0 to 255
---
1
F001
0
9B05
Teleprotection Terminal 2 ID
0 to 255
---
1
F001
0
9B06
Reserved (10 items)
0 to 1
---
---
F001
0
9B10
Teleprotection Input 1-n Default States (16 items)
0 to 3
---
1
F086
0 (Off)
9B30
Teleprotection Input 2-n Default States (16 items)
0 to 3
---
1
F086
0 (Off)
9B50
Teleprotection Output 1-n Operand (16 items)
0 to 65535
---
1
F300
0
9B70
Teleprotection Output 2-n Operand (16 items)
0 to 65535
---
1
F300
0
Teleprotection Inputs/Outputs Commands (Read/Write Command)
9B90
Teleprotection Clear Lost Packets
0 to 1
---
1
F126
0 (No)
Teleprotection Channel Tests (Read Only)
9B91
Teleprotection Channel 1 Status
0 to 2
---
1
F134
1 (OK)
9B92
Teleprotection Channel 1 Number of Lost Packets
0 to 65535
---
1
F001
0
9B93
Teleprotection Channel 2 Status
0 to 2
---
1
F134
1 (OK)
9B94
Teleprotection Channel 2 Number of Lost Packets
0 to 65535
---
1
F001
0
9B95
Teleprotection Network Status
0 to 2
---
1
F134
2 (n/a)
9BA0
Teleprotection Channel 1 Input States
0 to 1
---
1
F500
0
9BA1
Teleprotection Channel 2 Input States
0 to 1
---
1
F500
0
9BB0
Teleprotection Input 1 States, 1 per register (16 items)
0 to 1
---
1
F108
0 (Off)
9BC0
Teleprotection Input 2 States, 1 per register (16 items)
0 to 1
---
1
F108
0 (Off)
Table B–9: MODBUS MEMORY MAP (Sheet 31 of 50)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание C60 UR series
Страница 2: ......
Страница 4: ......
Страница 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX...
Страница 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS...
Страница 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 98: ...3 48 C60 Breaker Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3...
Страница 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Страница 390: ...8 18 C60 Breaker Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8...
Страница 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Страница 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D...
Страница 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E...