GE Multilin
C60 Breaker Protection System
7-5
7 COMMANDS AND TARGETS
7.2 TARGETS
7
b) MAJOR SELF-TEST ERROR MESSAGES
The major self-test errors are listed and described below.
•
Latched target message
: Yes.
•
Description of problem
: Module hardware failure detected.
•
How often the test is performed
: Module dependent.
•
What to do
: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod-
ule (for example, F8L).
•
Latched target message
: Yes.
•
Description of problem
: One or more installed hardware modules is not compatible with the C60 order code.
•
How often the test is performed
: Module dependent.
•
What to do
: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod-
ule (for example, F8L).
•
Latched target message
: No.
•
Description of problem
: The configuration of modules does not match the order code stored in the C60.
•
How often the test is performed
: On power up. Afterwards, the backplane is checked for missing cards every five sec-
onds.
•
What to do
: Check all modules against the order code, ensure they are inserted properly, and cycle control power. If
the problem persists, contact the factory.
•
Latched target message
: No.
•
Description of problem
: A FlexLogic™ equation is incorrect.
•
How often the test is performed
: The test is event driven, performed whenever FlexLogic™ equations are modified
.
•
What to do
: Finish all equation editing and use self tests to debug any errors.
•
Latched target message
: No.
•
Description of problem
: The
PRODUCT SETUP
ÖØ
INSTALLATION
Ö
RELAY SETTINGS
setting indicates the C60 is not pro-
grammed.
•
How often the test is performed
: On power up and whenever the
PRODUCT SETUP
ÖØ
INSTALLATION
Ö
RELAY SETTINGS
setting is altered
.
•
What to do
: Program all settings and then set
PRODUCT SETUP
ÖØ
INSTALLATION
Ö
RELAY SETTINGS
to “Programmed”.
MODULE FAILURE___:
Contact Factory (xxx)
INCOMPATIBLE H/W:
Contact Factory (xxx)
EQUIPMENT MISMATCH:
with 2nd line detail
FLEXLOGIC ERROR:
with 2nd line detail
UNIT NOT PROGRAMMED:
Check Settings
Содержание C60 UR series
Страница 2: ......
Страница 4: ......
Страница 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX...
Страница 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS...
Страница 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 98: ...3 48 C60 Breaker Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3...
Страница 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Страница 390: ...8 18 C60 Breaker Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8...
Страница 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Страница 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D...
Страница 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E...