B-74
C60 Breaker Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
F605
ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT
STATUS
F606
ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT
F611
ENUMERATION: GOOSE RETRANSMISSION SCHEME
F612
UR_UINT16: FLEXINTEGER PARAMETER
This 16-bit value corresponds to the Modbus address of the
selected FlexInteger paramter. Only certain values may be used
as FlexIntegers.
Enumeration
Remote DPS input status
0
Intermediate
1
Off
2
On
3
Bad
Enumeration
Remote double-point status input
0
None
1
Remote input 1
2
Remote input 2
3
Remote input 3
↓
↓
64
Remote input 64
Enumeration
Configurable GOOSE retransmission scheme
0
Heartbeat
1
Aggressive
2
Medium
3
Relaxed
Содержание C60 UR series
Страница 2: ......
Страница 4: ......
Страница 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX...
Страница 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS...
Страница 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 98: ...3 48 C60 Breaker Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3...
Страница 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Страница 390: ...8 18 C60 Breaker Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8...
Страница 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Страница 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D...
Страница 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E...