Table 23. Alarm Codes Descriptions
Alarm
Code
Alarm
Type
Description
00
Major
The network address is not programmed.
01
Major
Improper firmware detected for this radio model.
04
Major
One or more of the programmable synthesizer loops is reporting an
out-of-lock condition.
08
Major
The system is reporting that it has not been calibrated. Factory calibra-
tion is required for proper radio operation.
10
Major
The DSP was unable to properly program the system to the appropriate
defaults. A hardware problem may exist.
12
Major
Receiver time-out alarm.
16
Minor
The unit address is not programmed.
17
Minor
A data parity fault has been detected on the DATA connector. This
usually indicates a parity setting mismatch between the radio and the
RTU.
18
Minor
A data framing error has been detected on the DATA connector. This
may indicate a baud rate mismatch between the radio and the RTU.
29
Minor
RF output power fault detected. (Power differs by more than 2 dB from
set level.) Often caused by high antenna system SWR. Check antenna,
feedline and connectors.
30
Minor
The system is reporting an RSSI reading below –105 dBm.
31
Minor
The transceiver’s internal temperature is approaching an out-of-toler-
ance condition. If the temperature drifts outside of the recommended
operating range and the transceiver may fail.