Setting up an Output Group
Before you begin
Before you begin, you should complete an Output Group
Programming Worksheet (Figure 4-8) for each Output group.
Keep a copy for your records.
To set up an Output Group:
1. On the control panel, press Menu.
2. Choose Login then enter the password required for Level 4
access.
3. Choose Program > Configure > Output.
4. To program a new Output group, choose Add.
— or —
To edit an existing Output group, choose Edit, select the
group from the pick list, and then press Enter.
5. Add the responses.
6. After you finish entering the responses, you should review
them to make sure they are correct.
Adding a response that activates an
output circuit
1. Choose Responses.
2. Choose Active or Trouble
3. Choose Add > Relay, then enter the circuit address where
CC is the card number and DDD is the circuit number.
4. Choose the activation setting.
5. Choose Exit > Save Edits.
Adding a response that activates a
delay
1. Choose Responses.
2. Choose Active or Trouble.
3. Choose Add > Delay.
4. Choose Delay Type, then choose when to initiate the delay
response.
5. Choose Delay Time, press Del four times, and then enter
how many seconds you want the delay to last.
6. Choose Exit > Save Edits.
Technical Manuals Online! - http://www.tech-man.com
Содержание QS4
Страница 22: ...Product description 1 14 QS4 Technical Reference Manual Technical Manuals Online http www tech man com ...
Страница 122: ...System calculations A 10 QS4 Technical Reference Manual Technical Manuals Online http www tech man com ...
Страница 129: ...Barcode library QS4 Technical Reference Manual B 7 ZONE Technical Manuals Online http www tech man com ...
Страница 130: ...Barcode library B 8 QS4 Technical Reference Manual Technical Manuals Online http www tech man com ...
Страница 138: ...SIGA REL programming C 8 QS4 Technical Reference Manual Technical Manuals Online http www tech man com ...