Installation
QS4 Technical Reference Manual
2.9
ZR8 Relay Card jumpers
JP1 – JP8 configure which relay contacts are
present on the terminal connections for R1 – R8,
respectively.
The normal operating state of the relay (on or off
when the panel is normal) determines whether
the terminal connections are normally-open or
normally-closed.
The figure to the right shows the relay contact
positions when the relay is turned off.
R4+
R4–
JP4
RS485 (NT–A) Class A Card jumpers
JP1 configures ground fault supervision for
Class A remote annunciators.
•
Set a shorting plug across JP1–1 and JP1–2
when the PS6 powers the remote
annunciator and provides ground fault
supervision
•
Set a shorting plug across JP1–2 and JP1–3
when an external supply powers the remote
annunciator and provides ground fault
supervision
JP1
1
2
3