SIGA-REL programming
C.6
QS4 Technical Reference Manual
¨
¨
¨
¨
Create a response that activates
the prerelease circuits when
someone presses the Drill switch
Note:
Create this response only if
required. Pressing Drill will activate the
prerelease circuits but pressing Drill a
second time will not restore the
prerelease circuits. You must press
Reset to silence the prerelease circuits.
1. Click the Devices tab then select the Show Pseudo Points
check box.
2. Select the circuit labeled Drill (address 007).
3. Click the Responses tab, click the Response Type arrow,
and then select Active.
4. Click Outputs, select the device labeled SIGA REL1 A005
PRERELEASE 1&2, and then click OK.
¨
¨
¨
¨
Retrieve the loop data from the
SLIC
1. Click Configure, then click Cabinets.
2. Select the SLIC connected to the SIGA–REL then click
Configure.
3. Set the Communications Port setting for the COM port used
to connect the service computer to the control panel.
4. Click Retrieve Signature Data
5. After the upload has finished, click OK.
¨
¨
¨
¨
Reconcile the actual and
expected data
Caution:
Clicking Accept Actual will
enter the selected device into the
database with its current programmed
parameters. This will corrupt the
database if you have already entered
the device.
1. Click the Mapping tab, then click Model.
2. Look for a string of at least six RELs marked with red
backgrounds and double-click the first REL in the string.
3. If the serial number displayed in the Module Properties
dialog is not the same as the serial number shown on the
bar code attached to the SIGA–REL, click Close, and then
double-click the next REL in the string.
4. If the serial numbers are the same:
Click Select Expected.
In the Module Selection dialog, select the row that has the
REL with the Monitor device type and marked SIGA–REL1
A001 Abort SW, then click OK.
Click Close.
5. Select the next REL then click Select Expected.
In the Module Selection dialog, select the row that has the
REL with the Output device type and marked SIGA–REL1
A003 Release 1&2, then click OK.
Click Close.
6. Select the next REL then click Select Expected.
In the Module Selection dialog, select the row that has the
REL with the Output device type and marked SIGA–REL1
A005 Prerelease 1&2, then click OK.
Click Close.
Technical Manuals Online! - http://www.tech-man.com
Содержание QS4
Страница 22: ...Product description 1 14 QS4 Technical Reference Manual Technical Manuals Online http www tech man com ...
Страница 122: ...System calculations A 10 QS4 Technical Reference Manual Technical Manuals Online http www tech man com ...
Страница 129: ...Barcode library QS4 Technical Reference Manual B 7 ZONE Technical Manuals Online http www tech man com ...
Страница 130: ...Barcode library B 8 QS4 Technical Reference Manual Technical Manuals Online http www tech man com ...
Страница 138: ...SIGA REL programming C 8 QS4 Technical Reference Manual Technical Manuals Online http www tech man com ...