Appendix 2
Below is an example of a typical text file that can be sent to/from the COMBI system.
PLEASE NOTE:
1) ‘ : ‘ = Direct Sensor, ‘ * ” = Addressable Sensor
2) Lines of the same command but different addresses have been deleted
3) The difference between patterns and groups is that there are 16 patterns, and 8 groups.
Groups can only be used to control a single relay per event.
Should the user require two or more relays to be activated by a single event, patterns MUST be used.
Patterns primarily output to the first 16 relays on the 32 way relay card.
We then tell the control unit to mimic 7 of these relays by
•
going into option #23 (“event to relay 64)
•
Pressing ‘select’ 12 times so that “L,H,O,F,o1, o2, o3, o4” is displayed
•
Exiting
The Control unit is now setup to mimic 7 relays of the 32 way relay PCB
Combi Text File Command (Summarised) Description
Data to PC from panel address 1 :=4-20 and *=Addr
Note letters after : and * are case sensitive.
:c,
NAME OF COMPANY Tel: # # # # # #
:Seconds to alarm 1, 30,
*Seconds to alarm 1, 5,
:Alarmdir LHO 1,RRR
*Alarmdir LHO 1,RRR
:a1,1
:a2,1
:a3,1
:a4,1
:a5,1
:a6,2
:a7,1
:a8,1
Group87654321
:g01,00000001
Group87654321
*g01,00001001
:T1,LEL.SENSOR.1........,
*T1 ,O2.SENSOR.1.........,
*T2 ,boiler room…….,
:G1,%LeL ,
:unlatchedAlarm 1
*unlatchedAlarm 1
:LoDirAlarm 1 ,200,
:HiDirAlarm 1 ,400,
:OrDirAlarm 1 ,999,
*LoCanAlarm 1 ,190,
*HiCanAlarm 1 ,170,
*OrCanAlarm 1 ,250,
Event to Relay (Note keep in correct sequence)
Direct Chan 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
:Fault 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0,
:first alrm 4, 5, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0,
:second alrm 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0,
:third alrm 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0,
Addres Chan 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
*Fault 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0,
*first alrm 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0,
*second alrm 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0,
*third alrm , 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0,
Addres Chan 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
*Fault 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0,
*first alrm 6, 6, 6, 6, 6, 6, 6, 6, 6, 6, 6, 6, 6, 6, 6, 6,
*second alrm 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0,
*third alrm 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0,
35
Start of text file
Any text can be put here up to 40 characters
(x16) – the period of time that the sensor must detect the gas before it activates the control unit alarm
(x64) - the period of time that the sensor must detect the gas before it activates the control unit alarm
(x16) – Alarm direction (Lo / Hi / OR). R=Rising, F=Falling
(x64) - Alarm direction (Lo / Hi / OR). R=Rising, F=Falling
‘Group’ setup.
a1, a2 etc.. is the relay reference.
It determines how many alarms there needs to be before each group relay activates
Example: Group #6 need two sensors to be in alarm for relay activates
Direct channel #1 is in group 1
CAN channel #1 is in group 1 also, and in group 4
(x16) –Text for direct sensors connected. (E.g. this could represent the location of the sensor:
- i.e. boiler house, pump room etc..)
(x64) - List of addressable sensors connected.
You can also set the name of the sensor: (ie boilerhouse, pump room etc..)
(x16) – Direct Gas type
(x16) Direct alarms – ‘latchedalarm #’ or ‘unlatchedalarm #’
(x64) Addressable alarms – ‘latchedalarm #’ or ‘unlatchedalarm #’
(x16) Direct ‘Low’ alarm level.
Note: values are 1 significant figure – e.g ‘200’ = ‘20.0’ – (using list of direct sensors connected)
(x16) Direct ‘High’ alarm level.
Note: values are 1 significant figure – e.g ‘400’ = ‘40.0’
(x16) Direct ‘Overrange’ alarm level.
Note: values are 1 significant figure – e.g ‘999’ = ’99.9’
(x64) Addressable ‘Low’ alarm level.
Note: values are 1 significant figure – e.g ‘190’ = ’19.0’ (Oxygen would be ‘FFR’)
(x64) Addressable ‘High’ alarm level.
Note: values are 1 significant figure – e.g ‘170’ = ’17.0’
(x64) Addressable ‘High’ alarm level. Note: values are 1 significant figure – e.g ‘250’ = ’25.0’
Each event can drive 1 relay of the 64 external relay card.
Determines which relays activate for each direct channel on each of the 4 alarm types
In this example, relay 4 will trigger if direct chan 1 goes into ‘Lo’ alarm, and relay 5 will trigger for
channel 2
Note this is where Voting can be introduced (described above)
Note: no same relay can be used for two events
See above – but for addressable sensors 1-16
See above – but for addressable sensors 17-32