31]
LTEL, STEL Alarms
This menu allows you to set the time weighted average alarms for groups 5, 6, 7 and 8.
32]
Default Sections
Sometimes it is required to default part of the data in the panel and this menu allows you to do
this. (Some options are repeats of other menus) Pressing
SELECT (3)
moves to the next option
and pressing
+ (4)
defaults the option displayed.
The options are:-
Clear event log
Clears all events in the 99 event log
Default Modbus/Canbus
Defaults baud rate to 9600 and address 1
Default gas type to Flam
All sensors become FLAM type
Default Line text
Defaults to 4-20 text or CAN text
Default event to relay
All events do not drive any of the 64 remote relays
33]
Change Engineer’s Password
The engineer's password can be changed from this menu.you will be prompted to enter a new
code twice via the buttons. Pressing
SELECT (3)
will exit this menu.
Note:
The user password cannot be changed.
34]
Set Modbus Baud
This menu allows you to change the Baud rate used by the Modbus (default is 9600). The options
are 19200, 9600, 4800 bits per second and these are altered using the UP (1) and DOWN (5)
buttons, Pressing SELECT (3) will exit from this menu.
35]
Set Power Alarms
The panel detects both mains power and battery/DC power. When only one power source is in
use it is convenient to disable the loss detection of the other source so that the panel is not in
continuous fault. This menu allows you to inhibit the battery alarm first and by pressing
SELECT
(3)
then the mains alarm. The
+ (4)
and
– (2)
buttons toggle whether or not each alarm is
inhibited, this is displayed on the LCD. Pressing
SELECT (3)
will exit this menu.
36]
Set Energised Relays
This menu allows relays to be set as normally energised (=1) or de-energised (=0). 8765FOHL
represents the 8 on board relays
gfedcba987654321 represents the first 16 external relays
Using
+ (4)
and
– (2)
buttons, the small cursor moves along a pattern of ones and zeros which
represent the normally de-energised or energised setting and this can be changed using the
UP
(1)
and
DOWN (5)
buttons.
Press
SELECT (3)
to exit this menu.
34